Chapter (2) 2.1 Air break circuit breaker 2. 1. 1. Air-break Circuit-b การแปล - Chapter (2) 2.1 Air break circuit breaker 2. 1. 1. Air-break Circuit-b ไทย วิธีการพูด

Chapter (2) 2.1 Air break circuit b

Chapter (2) 2.1 Air break circuit breaker 2. 1. 1. Air-break Circuit-breaker The air at atmospheric pressure is used as an arc extinguishing medium in Air-Break Circuit-Breakers. This circuit breaker employs the high resistance interruption principle. the arc is rapidly lengthened by means of the arc runners and arc chutes and the resistance of the arc is increased by cooling, lengthening and splitting the arc. The arc resistance increases to such an extent that the voltage drop across the arc becomes more than the supply voltage and the arc gets extinguished. Magnetic field is utilized for lengthening the arc in high voltage air-break circuit-breakers. Air-break circuit breakers are used in D.C. circuit and a.c. circuits up to 12KV. The air-break circuit breakers are generally indoor type and installed on vertical panels or indoor draw-out type switchgear. A.C. air circuit breakers are widely used in indoor medium voltage and low voltage switchgear. Typical reference values of ratings of air-break circuit breaker are: 460 V, 400-3500 A, 40-75 KA 3.3 KV, 400-3500 A, 13.1-31.5 KA 6.6 KV, 400-2400 A, 13.1-20 KA 2. 1. 2. Construction of Air-break Circuit-breaker In the air-break circuit-breaker the contact separation and arc extinction takes place in air at atmospheric pressure. As the contacts are opened, arc is drawn between them. The arc core is a conducting 'path' of plasma. The surrounding medium contains ionized air. By cooling the arc, the diameter of arc core is reduced. The arc is extinguished by lengthening the arc, cooling the arc and splitting the arc. The arc resistance is increased to such an extent that the system voltage cannot maintain the arc and the arc get extinguished. This type of breaker is used for medium and low voltages. There are two sets of contacts : Main contacts (1) and Arcing contacts (2). Main contacts conduct the current in closed position of the breaker. They have low contact resistance and are silver plated. The arcing contacts (2) are hard, heat resistance and are usually of copper alloy. While opening the contacts, the main contacts dislodge first. The current is shifted to the arcing contacts. The arcing contacts dislodge later and arc is drawn between them (3). This arc is forced upwards by the electromagnetic forces and thermal action. The arc ends travel along the arc Runners (Arcing horns). The arc moves upwards and is split by arc splitter plates (arc chutes) (5) as shown by the arrow (4). The arc extinguished by lengthening, cooling, splitting etc. In some breakers the arc is drawn in the direction of the splitter by magnetic field. Furthermore, air-break circuit-breaker have been developed with current limiting feature, magnetic blow-up of arc, etc. Air break a.c. circuit breakers are widely used for industrial switchgear, auxiliary switchgear in generation station. Air break principle employing lengthening of arc, arc runners, magnetic blow-ups are used for d.c. circuit breaker up to 15 KV.
Circuit Breakers & Substations 4th Y ear Electrical Power Eng. Dep.
Prof. Dr. Sayed A. Ward Eng. Essam M. Shaalan Page 27
2. 1. 3. Air-break Circuit-breaker (Miniature and Molded-Case C.B) These are used extensively in low voltage domestic, commercial and industrial applications. They replace conventional fuses and combine the features of a good HRC fuse and a good switch. Fig.2.1 The internal details of a 10 ampere European DIN rail mounted thermal-magnetic circuit breaker For normal operation, it is used as a switch. During over loads or faults, it automatically trips off. The tripping mechanism is actuated by magnetic (part 7) and thermal sensing devices (part5) provide within the MVB. Tripping mechanism and the terminal contacts (part4) are assembled in a molded case, molded out of thermosetting powders. They ensure high mechanical strength, high dielectric strength and virtually no ageing. The current carrying parts (part3) are made out of electrolytic copper or silver alloy depending upon the rating of the breaker. All other metal parts are of non-ferrous, non rusting type. Sufficient cross section for the current carrying parts is provided to ensure low temperature rise even under high ambient temperature environment. The arc chute (part8) has a special construction which increase the length of the arc by the magnetic field created by the arc itself and the arc chute is so placed in the breaker that the hot gases may not come in contact with any of the important parts of the breaker. The breakers have unit construction whereby multiple pole breakers can be made by assemble of single pole breakers. Figure contents:
1. Actuator lever - used to manually trip and reset the circuit breaker. Also indicates the status of the circuit breaker (On or off /tripped). Most breakers are designed so they can still trip even if the lever is held or locked in the on position. This is sometimes referred to as "free trip" or "position trip" operation.
2. Actuator mechanism - forces the contacts together or apart.
3. Contacts - Allow current to flow when touching and break the flow of current when moved apart.
Circuit Breakers & Substations 4th Y ear Electrical Power Eng. Dep.
Prof. Dr. Sayed A. Ward Eng. Essam M. Shaalan Page 28
4. Terminals
5. Bimetallic strip
6. Calibration screw - Allows the manufacture to precisely adjust the trip current of the device after assembly.
7. Solenoid
8. Arc divider / extinguished
Typical Rating of MCB: Current Rating: 5, 10, 15, 20, 30, 40, 50, 60 Amp. Also, 0.5, 0.75, 1, 2, 2.5, 3, 3.5, 6, 7.5, 8, 10, 12, 25, 35, 45, 55 Amp. Voltage Rating: 240 V/415 V AC; 50 V/11 V DC Breaking Capacity: AC: 3 KA at 415 V DC: 3 KA at 50 V (non-inductive), 1 KA at 110 V (non-inductive). Typical Examples for AC MCB MCB DOM (6, 10, 16, 20, 25, 32, 40, 50, 63A) 4.5kA – 1, 2, 3, 4 poles MCB iK60 (6, 10, 16, 20, 25, 32, 40, 50, 63A) 6kA – 1, 2, 3 poles MCB iC60N (2, 3, 6, 10, 16, 20, 25, 32, 40, 50, 63A) 10kA – 1, 2, 3, 4 poles MCB iC60H (6, 10, 16, 20, 25, 32, 40, 50, 63A) 15kA – 1, 2, 3, 4 poles MCB iC60L (10, 16, 20, 25, 32, 40, 50, 63A) 15, 20, 25kA – 1, 2, 3, 4 poles MCB C120N (80, 100, 125A) 10kA – 1, 2, 3, 4 poles MCB C120H (80, 100, 125A) 15kA – 1, 2, 3, 4 poles Typical Examples for DC MCB MCB C60H (1, 2, 3, 4, 5, 6, 10, 13, 15, 16, 20, 25, 30, 32, 40, 50, 63A) 10kA – 1, 2 poles Typical Examples for AC MCCB MCCB EZC100F (15, 20, 25, 30, 40, 50, 60, 75, 80, 100A) 10kA – 1, 2, 3, 4 poles MCCB EZC100N (15, 20, 25, 30, 40, 50, 60, 75, 80, 100A) 18kA – 1, 2, 3, 4 poles
MCCB EZC100H (15, 20, 25, 30, 40, 50, 60, 75, 80, 100A) 30kA – 1, 2, 3, 4 poles MCCB EZC250N (100, 125, 150, 160, 175, 200, 225, 250A) 25kA – 3, 4 poles MCCB EZC250H (100, 125, 150, 160, 175, 200, 225, 250A) 36kA – 3, 4 poles MCCB EZC400N (250, 300, 320, 350, 400A) 36kA – 3, 4 poles MCCB EZC400H (250, 300, 320, 350, 400A) 50kA – 3, 4 poles
Circuit Breakers & Substations 4th Y ear Electrical Power Eng. Dep.
Prof. Dr. Sayed A. Ward Eng. Essam M. Shaalan Page 29
2.2. Air-Blast Circuit-Breaker 2.2.1 Introduction Air blast circuit breakers are used today from 11 to 1100 KV, for various application. They offer several advantages such as faster operations, suitability for related operation, auto-reclosure, unit type multi-break construction, simple, assembly, modest maintenance, etc. A compressor plant is necessary to maintain high air pressure in the receiver. Air-blast circuit breakers operate repeatedly. Air-blast circuit breakers are used for interconnected lines and important lines when rapid operation is desired. 2.2.2 Construction of Air-Blast Circuit-Breaker In air blast circuit breaker (also called compressed air circuit breaker) high pressure air is forced on the arc through a nozzle at the instant of contact separation. The ionized medium between the contacts is blown away by the blast of the air. After the arc extinction the chamber is filled with high pressure air, which prevents restrike. In some low capacity circuit breakers, the isolator is an integral part of the circuit breaker. The circuit breaker opens and immediately after that the isolator opens, to provide addition gap. In EHV circuit of today, isolators are generally independently mounted (Fig. 2.2). ( a ) Schematic construction
Circuit Breakers & Substations 4th Y ear Electrical Power Eng. Dep.
Prof. Dr. Sayed A. Ward Eng. Essam M. Shaalan Page 30
( b ) Principle
Figure 2.2 Air blast circuit breaker isolator connection Figure 2.3 shows one pole of the EHV air blast circuit breaker. In the complete assembly there are three identical poles. Figure 2.3 One pole of an extra high voltage air blast circuit breaker
Circuit Breakers & Substations 4th Y ear Electrical Power Eng. Dep.
Prof. Dr. Sayed A. Ward Eng. Essam M. Shaalan Page 31
Description: High pressure air between 20 to kgf/cm2, is is stored in the air reservoir (item 1 in Fig. 2.3). Air is taken from compressed air system. Three hollow insulator columns (item 2) are mounted on the resrvoir with valves (6) at their base. The double arc extinguishing chambers (3) are mounted on the top of the hollow insulator chambers. The current carrying parts (7) connect the three arc extinction chambers to each other in series and the pole to the neighboring equipment. Since there exist a very high voltage between the conductor and the air reservoir, the entire arc extinction chamber assembly is mounted on insulators. The details of the double arc extinction chambers (3) are shown in Fig. 2.4. Since there three double arc extinction poles in series, there are six breakers per pole. Each arc extinction chamber (Fig. 2.4) consists of one twin fixed contact. There are two moving contacts which are shown in the closing process. The moving contacts can move axially so as to open or close. Its position open or close depends on air pressure and spring pressure. Figure 2.4 Extra high voltage air blast circuit breaker
The operation mechanism (item 4 in Fig. 2.3) operates the rods (item 5) when it ge
0/5000
จาก: -
เป็น: -
ผลลัพธ์ (ไทย) 1: [สำเนา]
คัดลอก!
บทที่ 2.1 (2) อากาศแบ่งวงจรตัด 2 1. 1 ใช้อากาศแบ่งเบรกอากาศที่ความดันบรรยากาศเป็นอาร์ extinguishing กลางในอากาศแบ่งเบรคเกอร์ ตัดวงจรนี้ใช้หลักการหยุดชะงักของความต้านทานสูง อาร์คเป็น lengthened อย่างรวดเร็ว โดยรอบชิงชนะเลิศส่วนโค้ง และ chutes อาร์คและความต้านทานของส่วนโค้งจะเพิ่ม ทางระบายความร้อน เพิ่มความยาวของแบ่งอาร์ค ต้านทานส่วนโค้งเพิ่มถึงขนาดว่า หล่นแรงข้ามอาร์คจะเพิ่มมากขึ้นกว่าอุปทาน แรงและส่วนโค้งจะยกเลิก สนามแม่เหล็กจะใช้สำหรับเพิ่มความยาวของส่วนโค้งในแรงดันสูงแอร์เบรกเบรก แอร์เบรกเบรกจะใช้ในวงจรดีซีและเอซีวงจรถึง 12KV แอร์เบรกเบรกชนิดภายในอาคารโดยทั่วไป และติดตั้งในแนวตั้งแผงหรือสวิตช์ในร่มวาดออกประเภท ชื่อแอร์เบรคเกอร์ใช้สวิตช์แรงดันต่ำและแรงดันปานกลางในร่ม ค่าอ้างอิงโดยทั่วไปของการจัดอันดับของเบรกเบรกอากาศ: 460 V, 400-3500 A, 40-75 KA 3.3 KV, 400-3500 A, 13.1 ยาว 31.5 KA 6.6 KV, 2 KA 400 2400 A, 13.1-20 1. 2 การก่อสร้างตัดวงจรเบรกอากาศในอากาศแบ่งเบรคเกอร์ติดต่อแยกและโค้งสูญพันธุ์เกิดขึ้นในอากาศที่ความดันบรรยากาศ เป็นผู้ติดต่อจะเปิด เป็นวาดส่วนโค้งระหว่าง หลักส่วนโค้งจะทำ 'เส้นทาง' ของพลาสม่า กลางโดยรอบประกอบด้วยอากาศ ionized เส้นผ่าศูนย์กลางของส่วนโค้งหลักจะลดลง โดยการทำความเย็นส่วนโค้ง อาร์คเป็นยกเลิก ทางยาวของอาร์ค เย็นอาร์คแบ่งอาร์ค ต้านทานของส่วนโค้งจะเพิ่มระดับแรงดันระบบไฟฟ้าไม่สามารถเก็บรักษาอาร์คและอาร์คได้ยกเลิก เบรกเกอร์ชนิดนี้ใช้สำหรับแรงดันกลาง และต่ำ มีอยู่สองชุดติดต่อ: ติดต่อหลัก (1) และ Arcing ติดต่อ (2) ผู้ติดต่อหลักดำเนินการปัจจุบันในตำแหน่งปิดของการตัด พวกเขามีความต้านทานต่ำที่ติดต่อ และจะชุบเงิน ติดต่อ arcing (2) ยากต้านทานความร้อน และมักจะมีโลหะผสมทองแดง ขณะเปิดผู้ติดต่อ ผู้ติดต่อหลักไล่ออกก่อน ปัจจุบันจะเปลี่ยนติดต่อ arcing ติดต่อ arcing ไล่ออกในภายหลัง และเป็นวาดส่วนโค้งระหว่างพวกเขา (3) โค้งนี้บังคับขึ้น โดยกองกำลังของแม่เหล็กไฟฟ้าและการระบายความร้อน อาร์คสิ้นสุดลงไปตามส่วนโค้งรอบชิงชนะเลิศ (Arcing แตร) อาร์คย้ายขึ้น และแบ่งตามแผ่นแยกอาร์ค (arc chutes) (5) ดังแสดง ด้วยลูกศร (4) ส่วนโค้งยกเลิกตามยาวของ ความเย็น แบ่งฯลฯ ในบางเบรคเกอร์ อาร์คออกในทิศทางของการแยก โดยสนามแม่เหล็ก นอกจากนี้ แอร์เบรกเบรกได้รับการพัฒนา มีลักษณะจำกัดปัจจุบัน blow-up แม่เหล็กโค้ง ฯลฯ แอร์แบ่งชื่อเบรคเกอร์ใช้สำหรับอุตสาหกรรม switchgear สวิตช์ตัดเสริมในการสร้างสถานี หลักการแบ่งอากาศที่ใช้เพิ่มความยาวของส่วนโค้ง ส่วนโค้งรอบชิงชนะเลิศ blow-ups แม่เหล็กใช้สำหรับตัดวงจรดีซีถึง 15 KVเบรคเกอร์และสถานี 4 Y หูออกสุขาภิบาลพลังงานไฟฟ้ารศ.ดร. Sayed A. Ward สุขาภิบาลอิศอมม. Shaalan หน้า 272. 1 3. แบ่งอากาศเบรก (ขนาดเล็กและ C.B กรณี Molded) เหล่านี้ถูกใช้อย่างกว้างขวางในการใช้งานแรงดันต่ำภายในประเทศ ธุรกิจ และอุตสาหกรรม พวกเขาแทนฟิวส์ธรรมดา และรวมคุณลักษณะของชนวนเอชอาร์ซีดีและสลับดี Fig.2.1 รายละเอียดภายในของรถไฟยุโรปดิน 10 แอมแปร์เมาท์แม่เหล็กความร้อนเบรกเกอร์สำหรับการดำเนินงานปกติ ใช้เป็นสวิตช์ ระหว่างโหลดเกินหรือบกพร่อง มันอัตโนมัติทริปิด กลไก tripping เป็น actuated โดยแม่เหล็ก (ตอนที่ 7) และอุปกรณ์ที่ความร้อนไร้สาย (part5) ให้ภายใน MVB สะดุดกลไกและเทอร์มินัลติดต่อ (part4) มีประกอบในกรณีที่แม่พิมพ์ แม่พิมพ์จากผงเทอร์โมเซตติง พวกเขามั่นใจความแข็งแรงทางกลสูง แข็งแรงเป็นฉนวน และแทบไม่มีริ้วรอย ส่วนถือครองปัจจุบัน (part3) จะทำจาก electrolytic เงิน หรือทองแดงโลหะผสมขึ้นอยู่กับคะแนนที่ตัด ชิ้นส่วนโลหะอื่น ๆ ไม่ใช่เหล็ก ไม่พองชนิด พอข้ามส่วนสำหรับชิ้นส่วนถือครองปัจจุบันตั้งไว้ให้เพิ่มขึ้นอุณหภูมิต่ำแม้ภายใต้สภาพแวดล้อมที่อุณหภูมิสูง รางโค้ง (part8) มีการก่อสร้างพิเศษซึ่งเพิ่มความยาวของส่วนโค้งในสนามแม่เหล็กที่สร้างขึ้น โดยอาร์เอง และรางโค้งวางไว้ดังนั้นในการตัดที่ก๊าซร้อนอาจมาไม่ติดต่อใด ๆ ส่วนสำคัญของการตัด แบ่งการก่อสร้างหน่วยโดยแบ่งขั้วหลายสามารถทำได้โดยรวบรวมของเบรกเกอร์ขั้วเดียวได้ รูปเนื้อหา:1. actuator คาน - ใช้ในการเดินทางด้วยตนเอง และตั้งค่าเบรคเกอร์ นอกจากนี้ยัง บ่งชี้สถานะของเบรคเกอร์ (เปิด หรือปิด / tripped) เบรกเกอร์ส่วนใหญ่ถูกออกแบบมาเพื่อให้พวกเขายังคงสามารถใช้บริการแม้ว่าคันโยกถูกจัด หรือถูกล็อกในตำแหน่งที่ นี้บางครั้งเรียกว่าเป็น "บริการฟรี" หรือ "ตำแหน่งการเดินทาง" การดำเนินการ2. actuator กลไก - กองกำลังติดต่อกัน หรือแยก3. ติดต่อ - อนุญาตให้กระแสไหลเมื่อสัมผัส และทำลายการไหลของปัจจุบันเมื่อแยกย้ายเบรคเกอร์และสถานี 4 Y หูออกสุขาภิบาลพลังงานไฟฟ้ารศ.ดร. Sayed A. Ward สุขาภิบาลอิศอมม. Shaalan หน้า 284. เทอร์มินัล5. bimetallic strip6. เทียบเกลียว - ผลิตเพื่อปรับปรุงปัจจุบันเดินอุปกรณ์แม่นยำหลังจากแอสเซมบลีได้7. solenoid8. แบ่งอาร์ค / ยกเลิกโดยทั่วไปการจัดอันดับของ MCB: คะแนนปัจจุบัน: 5, 10, 15, 20, 30, 40, 50, 60 แอมป์ ยัง 0.5, 0.75, 1, 2, 2.5, 3, 3.5, 6, 7.5, 8, 10, 12, 25, 35, 45, 55 แอมป์ แรงดัน: V 240 415 V AC กำลังแบ่ง 11 V V DC 50: AC: 3 KA ที่ 415 V DC: 3 KA ที่ 50 V 1 (ไม่ใช่เหนี่ยว), KA ที่ 110 V (ไม่ใช่เหนี่ยว) ตัวอย่างทั่วไปสำหรับ AC MCB MCB โดม (6, 10, 16, 20, 25, 32, 40, 50, 63A) 4.5kA – 1, 2, 3, 4 เสา MCB iK60 (6, 10, 16, 20, 25, 32, 40, 50, 63A) 6kA – 1, 2, 3 เสา MCB iC60N (2, 3, 6, 10, 16, 20, 25, 32, 40, 50, 63A) 10kA – 1, 2, 3, 4 เสา MCB iC60H (6, 10 , 16, 20, 25, 32, 40, 50, 63A) 15kA – 1, 2, 3, 4 เสา MCB iC60L (10, 16, 20, 25, 32, 40, 50, 63A) 15, 20, 25kA – 1, 2, 3, 4 เสา MCB C120N (80, 100, 125A) 10kA – 1, 2, 3, 4 เสา MCB C120H (80, 100, 125A) 15kA – 1, 2, 3, 4 เสาตัวอย่างทั่วไปสำหรับ DC MCB MCB C60H (1 , 2, 3, 4, 5, 6, 10, 13, 15, 16, 20, 25, 30, 32, 40, 50, 63A) 10kA – 1, 2 เสาตัวอย่างทั่วไปสำหรับ AC MCCB MCCB EZC100F (15, 20, 25, 30, 40, 50, 60, 75, 80, 100A) 10kA – 1, 2, 3, 4 เสา MCCB EZC100N (15, 20, 25, 30, 40, 50, 60, 75, 80, 100A) 18kA – 1, 2, 3, 4 เสาMCCB EZC100H (15, 20, 25, 30, 40, 50, 60, 75, 80, 100A) 30kA – 1, 2, 3, 4 เสา MCCB EZC250N (100, 125, 150, 160, 175, 200, 225, 250A) 25kA-3, 4 เสา MCCB EZC250H (100, 125, 150, 160, 175, 200, 225, 250A) 36kA-3, 4 เสา MCCB EZC400N (250, 300, 320, 350, 400A) 36kA-3, 4 เสา MCCB EZC400H (250, 300 , 320, 350, 400A) 50kA-3, 4 เสาCircuit Breakers & Substations 4th Y ear Electrical Power Eng. Dep.Prof. Dr. Sayed A. Ward Eng. Essam M. Shaalan Page 292.2. Air-Blast Circuit-Breaker 2.2.1 Introduction Air blast circuit breakers are used today from 11 to 1100 KV, for various application. They offer several advantages such as faster operations, suitability for related operation, auto-reclosure, unit type multi-break construction, simple, assembly, modest maintenance, etc. A compressor plant is necessary to maintain high air pressure in the receiver. Air-blast circuit breakers operate repeatedly. Air-blast circuit breakers are used for interconnected lines and important lines when rapid operation is desired. 2.2.2 Construction of Air-Blast Circuit-Breaker In air blast circuit breaker (also called compressed air circuit breaker) high pressure air is forced on the arc through a nozzle at the instant of contact separation. The ionized medium between the contacts is blown away by the blast of the air. After the arc extinction the chamber is filled with high pressure air, which prevents restrike. In some low capacity circuit breakers, the isolator is an integral part of the circuit breaker. The circuit breaker opens and immediately after that the isolator opens, to provide addition gap. In EHV circuit of today, isolators are generally independently mounted (Fig. 2.2). ( a ) Schematic constructionCircuit Breakers & Substations 4th Y ear Electrical Power Eng. Dep.Prof. Dr. Sayed A. Ward Eng. Essam M. Shaalan Page 30( b ) PrincipleFigure 2.2 Air blast circuit breaker isolator connection Figure 2.3 shows one pole of the EHV air blast circuit breaker. In the complete assembly there are three identical poles. Figure 2.3 One pole of an extra high voltage air blast circuit breakerCircuit Breakers & Substations 4th Y ear Electrical Power Eng. Dep.Prof. Dr. Sayed A. Ward Eng. Essam M. Shaalan Page 31Description: High pressure air between 20 to kgf/cm2, is is stored in the air reservoir (item 1 in Fig. 2.3). Air is taken from compressed air system. Three hollow insulator columns (item 2) are mounted on the resrvoir with valves (6) at their base. The double arc extinguishing chambers (3) are mounted on the top of the hollow insulator chambers. The current carrying parts (7) connect the three arc extinction chambers to each other in series and the pole to the neighboring equipment. Since there exist a very high voltage between the conductor and the air reservoir, the entire arc extinction chamber assembly is mounted on insulators. The details of the double arc extinction chambers (3) are shown in Fig. 2.4. Since there three double arc extinction poles in series, there are six breakers per pole. Each arc extinction chamber (Fig. 2.4) consists of one twin fixed contact. There are two moving contacts which are shown in the closing process. The moving contacts can move axially so as to open or close. Its position open or close depends on air pressure and spring pressure. Figure 2.4 Extra high voltage air blast circuit breakerThe operation mechanism (item 4 in Fig. 2.3) operates the rods (item 5) when it ge
การแปล กรุณารอสักครู่..
ผลลัพธ์ (ไทย) 2:[สำเนา]
คัดลอก!
บทที่ (2) 2.1 เครื่องตัดวงจรแบ่ง 2. 1. 1. เครื่องทำลายวงจรเบรกเกอร์อากาศที่ความดันบรรยากาศจะถูกใช้เป็นสื่อกลางในการดับอาร์ในเครื่องหยุดวงจรเบรก ตัดวงจรนี้ใช้หลักการการหยุดชะงักความต้านทานสูง ส่วนโค้งที่มีความยาวอย่างรวดเร็วโดยวิธีการของนักวิ่งโค้งและโค้งปล่องและความต้านทานของอาร์จะเพิ่มขึ้นตามการระบายความร้อน, ความยาวและแยกส่วนโค้ง ความต้านทานโค้งเพิ่มขึ้นดังกล่าวเท่าที่แรงดันข้ามโค้งกลายเป็นมากกว่าแรงดันและอาร์ที่ได้รับการดับ สนามแม่เหล็กจะใช้สำหรับความยาวของส่วนโค้งในอากาศแรงดันสูงทำลายวงจรเบรกเกอร์ เบรกเกอร์วงจรเครื่องแบ่งที่ใช้ในวงจร DC และวงจร ac ถึง 12KV เบรกเกอร์วงจรเครื่องแบ่งเป็นประเภททั่วไปในร่มและติดตั้งบนแผงแนวตั้งหรือในร่มวาดออกสวิตช์ประเภท เบรกเกอร์วงจร AC อากาศที่มีการใช้กันอย่างแพร่หลายในแรงดันไฟฟ้าขนาดกลางในร่มและสวิตช์ไฟฟ้าแรงดันต่ำ ค่าอ้างอิงทั่วไปของการจัดอันดับของเบรกเกอร์เครื่องแบ่งเป็น: 460 V, 400-3500 A, 40-75 KA 3.3 KV, 400-3500 A, 13.1-31.5 KA 6.6 KV, 400-2400 A, 13.1-20 KA 2 . 1. 2. การก่อสร้างเครื่องทำลายวงจรเบรกเกอร์ในอากาศแบ่งเบรกเกอร์แยกการติดต่อและการสูญเสียที่เกิดขึ้นโค้งในอากาศที่ความดันบรรยากาศ ในฐานะที่เป็นรายชื่อที่จะเปิดโค้งจะถูกวาดขึ้นระหว่างพวกเขา หลักโค้งเป็นตัวนำ 'เส้นทาง' พลาสม่า กลางโดยรอบมีอากาศบริสุทธิ์ โดยการระบายความร้อนโค้งขนาดเส้นผ่าศูนย์กลางของแกนโค้งจะลดลง โค้งจะดับโดยความยาวของส่วนโค้งเย็นโค้งและแยกส่วนโค้ง ต้านทานโค้งที่มีการเพิ่มขึ้นดังกล่าวเท่าที่แรงดันไฟฟ้าที่ระบบไม่สามารถรักษาส่วนโค้งและโค้งรับดับ ชนิดของเบรกเกอร์นี้จะใช้สำหรับแรงดันไฟฟ้าขนาดกลางและต่ำ มีสองชุดของรายชื่อมีดังนี้: รายชื่อหลัก (1) และรายชื่อลอย (2) รายชื่อหลักดำเนินการในปัจจุบันอยู่ในตำแหน่งปิดเบรกเกอร์ พวกเขามีความต้านทานติดต่อต่ำและเงินชุบ ติดต่อ arcing (2) มีความยากทนต่อความร้อนและเป็นเรื่องปกติของโลหะผสมทองแดง ในขณะที่การเปิดรายชื่อผู้ติดต่อหลักขับไล่ครั้งแรก ปัจจุบันจะเลื่อนไปยังรายชื่อ arcing ติดต่อ arcing ขับออกไปในภายหลังและส่วนโค้งจะถูกวาดขึ้นระหว่างพวกเขา (3) โค้งนี้ถูกบังคับให้ขึ้นไปโดยกองกำลังไฟฟ้าและการกระทำความร้อน โค้งจบการเดินทางไปตามส่วนโค้งวิ่ง (แตร Arcing) โค้งย้ายขึ้นไปและถูกแบ่งโดยแยกแผ่นโค้ง (ปล่องโค้ง) (5) ที่แสดงโดยลูกศร (4) โค้งดับยาวระบายความร้อนแยกเบรกเกอร์ ฯลฯ ในบางโค้งจะถูกดึงไปในทิศทางของแยกโดยสนามแม่เหล็ก นอกจากนี้เครื่องหยุดพักเบรกเกอร์ได้รับการพัฒนาพร้อมกับคุณสมบัติการ จำกัด กระแสแม่เหล็กระเบิดขึ้นของส่วนโค้ง ฯลฯ เบรกเกอร์วงจรแบ่ง ac อากาศที่มีการใช้กันอย่างแพร่หลายสำหรับสวิตช์อุตสาหกรรมสวิตช์ช่วยในการสร้างสถานี เครื่องทำลายหลักการจ้างยาวของส่วนโค้งวิ่งโค้งแม่เหล็กพัดอัพที่ใช้สำหรับตัดวงจร dc ถึง 15 KV.
เบรกเกอร์แผงวงจรและ Substations 4 Y หูไฟฟ้าพลังงาน Eng dep.
ศ. ดร. วอร์ดเอ Sayed Eng Essam เมตร Shaalan หน้า 27
2. 1. 3. เครื่องทำลายวงจรเบรกเกอร์ (ขนาดเล็กและกรณีแม่พิมพ์ CB) เหล่านี้จะถูกใช้อย่างกว้างขวางในแรงดันต่ำในประเทศเชิงพาณิชย์และอุตสาหกรรม พวกเขาเปลี่ยนฟิวส์ธรรมดาและรวมคุณสมบัติของฟิวส์เหล็กแผ่นรีดร้อนที่ดีและสวิทช์ที่ดี Fig.2.1 รายละเอียดภายในของ 10 แอมป์ยุโรป DIN รถไฟติดตั้งตัวตัดวงจรความร้อนแม่เหล็กสำหรับการดำเนินงานปกติจะใช้เป็นสวิทช์ ในช่วงกว่าโหลดหรือความผิดพลาดก็ทริปปิดโดยอัตโนมัติ กลไกการสะดุดจะทำงานโดยสนามแม่เหล็ก (ตอนที่ 7) และอุปกรณ์ตรวจจับความร้อน (Part5) ให้ภายใน MVB กลไกการสะดุดและรายชื่อขั้ว (part4) จะประกอบในกรณีแม่พิมพ์ขึ้นรูปจากผงเทอร์โม พวกเขามั่นใจความแข็งแรงเชิงกลสูงความเป็นฉนวนสูงและแทบไม่มีริ้วรอย ส่วนการดำเนินการปัจจุบัน (ส่วนที่ 3) ที่ทำจากทองแดงด้วยไฟฟ้าหรือโลหะผสมเงินขึ้นอยู่กับคะแนนของเบรกที่ ทุกชิ้นส่วนโลหะอื่น ๆ ที่ไม่ใช่เหล็กชนิดที่ไม่เกิดสนิม ข้ามส่วนที่เพียงพอสำหรับการดำเนินการในส่วนที่ปัจจุบันมีให้เพื่อให้แน่ใจว่าอุณหภูมิที่เพิ่มขึ้นต่ำแม้ภายใต้สภาพแวดล้อมที่อุณหภูมิสูง รางโค้ง (part8) มีโครงสร้างพิเศษที่เพิ่มความยาวของส่วนโค้งโดยสนามแม่เหล็กที่สร้างขึ้นโดยอาร์ตัวเองและรางโค้งจะอยู่ในเครื่องบดที่ก๊าซร้อนอาจจะไม่เข้ามาติดต่อกับใด ๆ ของที่สำคัญ ส่วนของเบรกเกอร์ เบรกเกอร์มีการก่อสร้างโดยหลายหน่วยเบรกเกอร์เสาสามารถทำได้โดยการรวบรวมของเบรกเกอร์เสาเดียว เนื้อหารูป:
1 คันขับเคลื่อน - ใช้ในการเดินทางด้วยตนเองและการตั้งค่าเบรกเกอร์ ยังแสดงสถานะของการตัดวงจรนี้ (หรือปิด / สะดุด) เบรกเกอร์ส่วนใหญ่ได้รับการออกแบบเพื่อให้พวกเขายังคงสามารถเดินทางแม้ว่าคันจะจัดขึ้นหรือถูกขังอยู่ในตำแหน่ง นี่คือบางครั้งเรียกว่า "การเดินทางฟรี" หรือ "การเดินทางตำแหน่ง" การดำเนินการ.
2 กลไกการขับเคลื่อน - กองกำลังติดต่อด้วยกันหรือแยกออกจากกัน.
3 รายชื่อ - อนุญาตให้กระแสไหลเมื่อสัมผัสและทำลายการไหลของกระแสไฟฟ้าเมื่อย้ายออกจากกัน.
เบรกเกอร์แผงวงจรและ Substations 4 Y หูไฟฟ้าพลังงาน Eng dep.
ศ. ดร. วอร์ดเอ Sayed Eng Essam เมตร Shaalan หน้า 28
4. ขั้ว
5 แถบ bimetallic
6 สกรูสอบเทียบ - ช่วยให้การผลิตได้อย่างแม่นยำปรับในปัจจุบันการเดินทางของอุปกรณ์หลังจากที่การชุมนุม.
7 โซลินอย
8 แบ่ง Arc /
ดับการจัดอันดับโดยทั่วไปของMCB: คะแนนปัจจุบัน: 5, 10, 15, 20, 30, 40, 50, 60 แอมป์ นอกจากนี้, 0.5, 0.75, 1, 2, 2.5, 3, 3.5, 6, 7.5, 8, 10, 12, 25, 35, 45, 55 แอมป์ แรงดันไฟฟ้า: 240 V / 415 V AC; 50 V / 11 V DC ทำลายความจุ: AC: 3 KA ที่ 415 V DC: 3 KA 50 V (ที่ไม่ใช่อุปนัย) 1 KA 110 V (ที่ไม่ใช่อุปนัย) ตัวอย่างทั่วไปสำหรับ AC MCB MCB DOM (6, 10, 16, 20, 25, 32, 40, 50, 63A) 4.5kA - 1, 2, 3, 4 เสา MCB iK60 (6, 10, 16, 20, 25, 32, 40, 50, 63A) 6kA - 1, 2, 3 เสา MCB iC60N (2, 3, 6, 10, 16, 20, 25, 32, 40, 50, 63A) 10kA - 1, 2, 3, 4 เสา MCB iC60H (6, 10, 16, 20, 25, 32, 40, 50, 63A) 15kA - 1, 2, 3, 4 เสา MCB iC60L (10, 16, 20, 25, 32, 40, 50, 63A ) 15, 20, 25kA - 1, 2, 3, 4 เสา MCB C120N (80, 100, 125A) 10kA - 1, 2, 3, 4 เสา MCB C120H (80, 100, 125A) 15kA - 1, 2, 3 4 เสาตัวอย่างทั่วไปสำหรับซี MCB MCB C60H (1, 2, 3, 4, 5, 6, 10, 13, 15, 16, 20, 25, 30, 32, 40, 50, 63A) 10kA - 1, 2 เสาตัวอย่างทั่วไปสำหรับ AC MCCB MCCB EZC100F (15, 20, 25, 30, 40, 50, 60, 75, 80, 100A) 10kA - 1, 2, 3, 4 เสา MCCB EZC100N (15, 20, 25, 30, 40, 50, 60, 75, 80, 100A) 18kA - 1, 2, 3, 4 เสา
MCCB EZC100H (15, 20, 25, 30, 40, 50, 60, 75, 80, 100A) 30kA - 1, 2 , 3, 4 เสา MCCB EZC250N (100, 125, 150, 160, 175, 200, 225, 250A) 25kA - 3, 4 เสา MCCB EZC250H (100, 125, 150, 160, 175, 200, 225, 250A) 36kA - 3, 4 เสา MCCB EZC400N (250, 300, 320, 350, 400A) 36kA - 3, 4 เสา MCCB EZC400H (250, 300, 320, 350, 400A) 50KA - 3, 4
เสาวงจรแบ่งและSubstations 4 Y หู ไฟฟ้าพลังงาน Eng dep.
ศ. ดร. วอร์ดเอ Sayed Eng Essam เมตร Shaalan หน้า 29
2.2 เครื่องระเบิดเบรกเกอร์ 2.2.1 บทนำเบรกเกอร์วงจรระเบิดเครื่องใช้มาจนถึงปัจจุบัน 11-1100 KV สำหรับแอพลิเคชันต่างๆ พวกเขามีข้อได้เปรียบหลายอย่างเช่นการดำเนินงานได้เร็วขึ้นเหมาะสมสำหรับการดำเนินงานที่เกี่ยวข้องกับรถยนต์ Reclosure ประเภทหน่วยงานก่อสร้างหลายแบ่งง่ายประกอบการบำรุงรักษาเจียมเนื้อเจียมตัว ฯลฯ โรงงานอัดเป็นสิ่งที่จำเป็นในการรักษาความดันอากาศสูงในการรับสัญญาณ วงจรเครื่องระเบิดเบรกทำงานซ้ำ ๆ เบรกเกอร์วงจรเครื่องระเบิดที่ใช้สำหรับการเชื่อมต่อสายและสายที่สำคัญเมื่อการดำเนินการอย่างรวดเร็วเป็นที่ต้องการ 2.2.2 การสร้างเครื่องระเบิดเบรกเกอร์ในอากาศตัดวงจรระเบิด (ที่เรียกว่าตัดวงจรการบีบอัดอากาศ) อากาศแรงดันสูงถูกบังคับโค้งผ่านหัวฉีดในทันทีของการแยกการติดต่อ สื่อที่แตกตัวเป็นไอออนระหว่างรายชื่อที่จะถูกเป่าออกไปโดยการระเบิดของอากาศ หลังจากการสูญเสียส่วนโค้งในห้องที่เต็มไปด้วยอากาศแรงดันสูงซึ่งจะช่วยป้องกัน restrike ในบางความจุต่ำเบรกเกอร์วงจร isolator เป็นส่วนหนึ่งของการตัดวงจร เบรกเกอร์เปิดและทันทีหลังจากนั้น isolator เปิดเพื่อให้ช่องว่างนอกจากนี้ ในวงจร EHV วันนี้แยกมักจะติดตั้งอิสระ (รูป. 2.2) (ก)
การก่อสร้างแผนผังวงจรแบ่งและSubstations 4 Y หูไฟฟ้าพลังงาน Eng dep.
ศ. ดร. วอร์ดเอ Sayed Eng Essam เมตร Shaalan หน้า 30
(ข)
หลักการรูปที่2.2 การเชื่อมต่อวงจรระเบิดเบรกเกอร์แอร์ isolator รูปที่ 2.3 แสดงให้เห็นว่าหนึ่งในเสาของ EHV อากาศตัดวงจรระเบิด ในการชุมนุมที่สมบูรณ์มีสามเสาเหมือนกัน รูปที่ 2.3
หนึ่งของเสาไฟฟ้าแรงสูงพิเศษอากาศตัดวงจรระเบิดวงจรแบ่งและSubstations 4 Y หูไฟฟ้าพลังงาน Eng dep.
ศ. ดร. วอร์ดเอ Sayed Eng Essam เมตร Shaalan หน้า 31
คำอธิบาย: (. รายการที่ 1 ในรูปที่ 2.3) อากาศแรงดันสูงระหว่าง 20 ถึง kgf / cm2 จะถูกเก็บไว้ในอ่างเก็บน้ำอากาศ อากาศจะถูกนำมาจากระบบอัดอากาศ สามคอลัมน์ฉนวนกลวง (รายการที่ 2) ติดตั้งอยู่บน resrvoir กับวาล์ว (6) ที่ฐานของพวกเขา โค้งดับสองห้อง (3) ที่ติดตั้งอยู่ด้านบนของห้องฉนวนกลวง ส่วนการดำเนินการในปัจจุบัน (7) เชื่อมต่อสามห้องสูญพันธุ์อาร์ให้กับแต่ละอื่น ๆ ในชุดและเสาไปยังอุปกรณ์ที่อยู่ใกล้เคียง เนื่องจากมีแรงดันไฟฟ้าที่มีอยู่สูงมากระหว่างตัวนำและอ่างเก็บน้ำอากาศประกอบห้องสูญพันธุ์อาร์ทั้งหมดจะถูกติดตั้งอยู่บนฉนวน รายละเอียดของการสูญพันธุ์โค้งห้องคู่ (3) มีการแสดงในรูป 2.4 เนื่องจากมีสามเสาโค้งคู่สูญพันธุ์ในชุดมีหกเบรกเกอร์ต่อเสา แต่ละห้องสูญพันธุ์โค้ง (รูป. 2.4) ประกอบด้วยหนึ่งการติดต่อคงคู่ มีสองรายชื่อที่เคลื่อนไหวซึ่งจะแสดงในกระบวนการที่มีการปิด รายชื่อที่เคลื่อนไหวสามารถย้ายแกนเพื่อที่จะเปิดหรือปิด ตำแหน่งเปิดหรือปิดขึ้นอยู่กับความดันอากาศและความดันในฤดูใบไม้ผลิ รูปที่ 2.4 Extra
ตัดวงจรระเบิดอากาศแรงดันสูงกลไกการดำเนินการ(ข้อ 4 ในรูป. 2.3) ดำเนินแท่ง (รายการที่ 5) เมื่อมัน ge
การแปล กรุณารอสักครู่..
ผลลัพธ์ (ไทย) 3:[สำเนา]
คัดลอก!
บท ( 2 ) 2.1 อากาศตัดวงจรเบรกเกอร์ 2 1 . 1 . แบ่งอากาศเบรกเกอร์วงจรอากาศที่ความดันบรรยากาศ คือ ใช้เป็นสารในอากาศกลางโค้งเบรกเกอร์วงจรแบ่ง เบรกเกอร์วงจรนี้มีความต้านทานสูงขัดหลักการ โค้งยาวขึ้นอย่างรวดเร็ว โดยวิธีการอาร์คมาราธอนและร่มโค้งและความต้านทานของ Arc เพิ่มขึ้นจากความร้อนยาว และแยก ARC ความต้านทาน Arc เพิ่มขึ้นดังกล่าวเท่าที่แรงดันตกคร่อม อาร์คกลายเป็นมากกว่าอุปทานแรงดันอาร์คจะดับ แม่เหล็กใช้สำหรับยาวโค้งในอากาศเบรกเกอร์วงจรแบ่งแรงดันไฟฟ้าสูง เบรกเกอร์วงจรแบ่งอากาศใช้ในวงจรไฟฟ้ากระแสตรง วงจรไฟฟ้ากระแสสลับและถึง 12kv .อากาศตัดวงจรเบรกเกอร์โดยทั่วไปประเภทในร่มและติดตั้งบนแผงแนวตั้งหรือในร่มวาดออกประเภทสวิตช์ . เบรกเกอร์วงจรของอากาศที่ใช้กันอย่างแพร่หลายในแรงดันไฟฟ้าขนาดกลางในร่มและสวิตช์แรงดันต่ำ โดยทั่วไปค่าอ้างอิงของการจัดอันดับของเบรกเกอร์แอร์เบรค : 460 V , 400-3500 , 40-75 ค่ะ 3.3 กิโล 400-3500 , 13.1-31.5 กะ 6.6 กิโล 400-2400 , 13.1-20 กา 2 1 . 2 .การสร้างวงจรแบ่งอากาศในอากาศตัดวงจรเบรกเกอร์แยกติดต่อ และอาร์คการสูญพันธุ์เกิดขึ้นในอากาศที่ความดันบรรยากาศ เป็นผู้ติดต่อจะเปิด Arc วาดระหว่างพวกเขา อาร์คหลักคือการ ' เส้นทาง ' ของพลาสมา รอบกลางประกอบด้วยประจุอากาศ โดยอาร์เย็น เส้นผ่าศูนย์กลางของอาร์คหลักลดลงอาร์คจะดับตาม ยาวโค้งเย็น , ส่วนโค้งและแยก ARC ความต้านทาน Arc เพิ่มขึ้นถึงขนาดที่ไม่สามารถระบบรักษาแรงดันอาร์คและอาร์ครับดับ ของเบรกเกอร์ชนิดนี้ ใช้ ปานกลาง และต่ำนั้น มีสองชุดของการติดต่อ : ติดต่อหลัก ( 1 ) arcing ติดต่อ ( 2 )
การแปล กรุณารอสักครู่..
 
ภาษาอื่น ๆ
การสนับสนุนเครื่องมือแปลภาษา: กรีก, กันนาดา, กาลิเชียน, คลิงออน, คอร์สิกา, คาซัค, คาตาลัน, คินยารวันดา, คีร์กิซ, คุชราต, จอร์เจีย, จีน, จีนดั้งเดิม, ชวา, ชิเชวา, ซามัว, ซีบัวโน, ซุนดา, ซูลู, ญี่ปุ่น, ดัตช์, ตรวจหาภาษา, ตุรกี, ทมิฬ, ทาจิก, ทาทาร์, นอร์เวย์, บอสเนีย, บัลแกเรีย, บาสก์, ปัญจาป, ฝรั่งเศส, พาชตู, ฟริเชียน, ฟินแลนด์, ฟิลิปปินส์, ภาษาอินโดนีเซี, มองโกเลีย, มัลทีส, มาซีโดเนีย, มาราฐี, มาลากาซี, มาลายาลัม, มาเลย์, ม้ง, ยิดดิช, ยูเครน, รัสเซีย, ละติน, ลักเซมเบิร์ก, ลัตเวีย, ลาว, ลิทัวเนีย, สวาฮิลี, สวีเดน, สิงหล, สินธี, สเปน, สโลวัก, สโลวีเนีย, อังกฤษ, อัมฮาริก, อาร์เซอร์ไบจัน, อาร์เมเนีย, อาหรับ, อิกโบ, อิตาลี, อุยกูร์, อุสเบกิสถาน, อูรดู, ฮังการี, ฮัวซา, ฮาวาย, ฮินดี, ฮีบรู, เกลิกสกอต, เกาหลี, เขมร, เคิร์ด, เช็ก, เซอร์เบียน, เซโซโท, เดนมาร์ก, เตลูกู, เติร์กเมน, เนปาล, เบงกอล, เบลารุส, เปอร์เซีย, เมารี, เมียนมา (พม่า), เยอรมัน, เวลส์, เวียดนาม, เอสเปอแรนโต, เอสโทเนีย, เฮติครีโอล, แอฟริกา, แอลเบเนีย, โคซา, โครเอเชีย, โชนา, โซมาลี, โปรตุเกส, โปแลนด์, โยรูบา, โรมาเนีย, โอเดีย (โอริยา), ไทย, ไอซ์แลนด์, ไอร์แลนด์, การแปลภาษา.

Copyright ©2024 I Love Translation. All reserved.

E-mail: