The finished insulated conductor (any jacket, shield, and covering removed) shall have an insulation
resistance value of greater than 2.5 megohms based on 1000 feet (0.75 megohm based on one kilometer)
of conductor. The PTFE and ETFE insulation shall result in the full range of sizes of finished wire having
an insulation resistance not less than 1000 megohms based on 1000 conductor feet or 304 megohms
based on a conductor kilometer. The test is to be conducted in accordance with Insulation