Step Function comments
0 Burner running
1 Command Auto stop Dryer Burner = 1 From the sequence of Dryer in Alpha system,
2 Send Burner Stop signal to stop
Eclipse Burner
Delay Timer 1
3 Timer 1 Expired
Send Combustion fan Stop signal to
stop Eclipse Burner
4 Automatic Damper to Close position
5 Inlet Fan moves to Speed Setpoint 4
Cooling speed setpoint
Outlet Fan moves to Speed Setpoint 4
6 Check Feedback temperature reaches
below Cooling temperature setpoint
7 Stop Inlet and Outlet Fans Complete stop sequence
8 Wait for start command