4.7.1 Calibration of Curtains if Potentiometers are Used
The curtain closes; after the value remains the same for 15 seconds, the value is set as the closed curtain value. At this point the curtain opens and the value changes. When the value remains the same for 15 seconds, that value is set as the open curtain value. Afterwards the curtain closes again, and closing duration is measured, as well as the opening duration.
To stop the calibration process, press SELECT.
4.7.2 Calibration of Curtains if Potentiometers are Not Used
1. Set up the system with no potentiometers Go to SYSTEM, - Pot and select: 0.
2. Set up the close/open times for the curtains. It is very important to measure the time precisely.
3. Set up the number of steps for automatic calibration Go to SYSTEM - Cal. Steps
Example: If the number of steps is 50, then the controller opens the curtain every 50 movements of the curtain for the entire opening time and then returns the curtain to its previous position.