Further towards the main equipotential bonding bar, the lightning equipotential
bonding must also be implemented for cables of electrical and electronic systems at
this boundary of the zones. This equipotential bonding must be installed as close as
possible to the location where the lines and metal installations enter the building or
structure. The equipotential bonding conductor should be designed to be as short
(low impedance) as possible.