V. Set Parameter Range
1. Set the time between poppet valve and pulse valve to 1-250 seconds.
Press the "MODE" button, press "+" or "-" when the first letter is A on the monitor.
Adjust the time range to 1-250 seconds.
2. Set the time interval of pulse valve to 1-250 seconds.
Press the "MODE" button, press "+" or "-" when the first letter is B on the monitor.
Adjust the time range to 1-250 seconds.
3. Set the time between pulse valve and poppet valve closed to 1-250 seconds.
Press the "MODE" button, press "+" or "-" when the first letter is C on the monitor.
Adjust the time range to 1-250 seconds.
4. Set the opening time of pulse valve to 10-2500 milliseconds. (1:10)
Press the "MODE" button, press "+" or "-" when the first letter is D on the monitor.
Adjust the time range to 1-250 seconds.
(For example: 1.5 seconds = 1500 milliseconds, 1500 milliseconds = 150 × 101
milliseconds, showing as D150)
5. Set the time interval of poppet valve group to 1-250 seconds.
Press the "MODE" button, press "+" or "-" when the first letter is E on the monitor.
Adjust the time range to 1-250 seconds.
6. Set the cycle time to 0-250 seconds.
Press the "MODE" button, press "+" or "-" when the first letter is F on the monitor.
Adjust the time range to 0-250 seconds.
7. Set the blowing times of turndown set times to 1-25 times.
Press the "MODE" button, press "+" or "-" when the first letter is q on the monitor.
Adjust the cycle times range after turndown to 1-25 times.
8. Set the total channel number to 1-20 channels (poppet valve and pulse valve).
Press the "MODE" button, press "+" or "-" when the first letter is P on the monitor.
Adjust the total channel number range to 1-20 channels.
9. Set poppet valve mode and pulse valve mode
Means No.1 channel is poppet valve.
Means No.1 channel is pulse valve.
Press "MODE" button; the first and second letters are ON or OF on the monitor.
1) Press "+" or "-", select the mode wanted to be set.
2) Press "SET" cycle button, select ON to set the poppet valve mode; select OF to
set the pulse valve mode. ※ Mode must be set in every channel.
3) Repeat step 1 and 2 to continue setting other channels.
10. Set repeated blowing
If Pn channel needs repeated blowing, press the SET button when the controller