This relaying algorithm differentiates internal faults from the inrush and overexcitation conditions based on the on-line calculated flux in the core [14,15]. As its advantage,this approach ties together the cause of the problem (saturation of the core as a source of the current unbalance) with the phenomenon used for recognition (flux in the core).