The differential relay has an inherent dead band (Figure 8.4), compared to the pressure relay,
which is insensitive to winding fault location. If it is assumed that the pressure relay will always
operate for an internal fault, then the operation of the differential relay alone is a safe indication
that the fault is not within the transformer tank, and reclosing can be permitted.