4.5 Flame Arrester
Flame arrester shall be design, manufactured and test in accordance with standard API 2000 or UL525.
4.6 Detonation Arrester
Detonation arrester shall be design, manufactured and test in accordance with International standard.
4.7 Hydrocarbon (VOC) Analyzer
Hydrocarbon (VOC) Analyzer shall be designed and manufactured in accordance with the emission regulation stipulated by the Pollution Control Department as follows:
• Measurement of gas left In organic compounds Using Gas Chromatography. Measured using 18 method
(Method 18 : Measurement of Gaseous Organic Compound Emission by Gas Chromatography) as United States Environmental Protection Agency set or
• To measure the concentration of gas left. In the form of organic compounds Using a Flame Ionization Analyzer. Measured using 25A method
(Method 25A : Total Gaseous Organic Concentration Using a Flame Ionization Analyzer) as United States Environmental Protection Agency set or
• To measure the concentration of gas left. In the form of organic compounds Using a Nondispersive Infrared Analyzer. Measured using 25B method
(Method 25B : Determination of Total Gaseous Organic Concentration Using a Nondispersive Infrared Analyzer) as United States Environmental Protection Agency set or
• Measurement methods and other analysis tools, PCD announced in the Government Gazette.
4.8 Main MCC and Control system
4.8.1 Main MCC Produced by VDE ,IEC ,NEMA or ANSI Standard for 380/220 Volt 3 Phase 4 wire 50 Hz Qualifying requirements NEC Code Article 384 and qualified The EPA to use.
4.8.2 Switch or Circuit Breaker , Magnetic Starter & Overload , Contactor all items must be produced from the same place.
4.8.3 Switch or Circuit Breaker used in low voltage ,Frame size not smaller than required and is resistant short circuit current of not less than specified.
4.8.4 Equipment used in Wiring for motor control include Amp Meter can show value now start and run , Selector Switch can select Remote/Off/Local , Signal lamp can show status Run/Stop/Trip and Hour Meter Available Effectively equivalent to the original equipment.
4.8.5 Main MCC include Switch or Circuit Breaker and Magnetic Starter & Overload is consistent with the Motor Drive for pump control VRU systems as required.
4.8.5.1 Absorbent Supply Pump(Gasoline)
4.8.5.2 Absorbent Return Pump(Gasoline)
4.8.5.3 Condensate Pump
4.8.5.4 Sump Pump
4.8.5.5 Load Panel(LP) Main Power for Essential Load
4.8.5.6 Other Pump
4.8.5.7 Spare
Structure details
4.8.6 Frame steel minimum thickness 3 mm. welded or hold with bolt.
4.8.7 Wall steel minimum thickness 2 mm. Corrosion protection process and Spray dried paint overlay.
4.8.8 The device consists of a Busbars , Circuit Breaker , Magnetic Starter & Overload , Rail lines , Terminal , Cable , Metering and base for mounting and must be able to spare for MCC(Up to 25 HP) least 3 sets.
4.8.9 Can be opened The front and rear doors , Part installation Motor control as drawer and have Safety Lock Protection (Block set) make it easier to Maintenance equivalent to the original equipment.
4.8.10 Front doors use soft hinges.
4.8.11 Side walls have ventilation be enough Overlaid with Insect Screen and Dust Filter.
4.8.12 Plastic nameplate and Mimic Bus Diagram on Front doors.
4.8.13 All metal body Corrosion protection process and Spray dried paint overlay (Stove - Enamelled Paint).
4.8.14 Hinged doors must be grounded with copper wire.
Technical details
4.8.15 Busbar is Copper purity 98% and must have Ground Bus at the rear bottom corner and Neutral Bus at the rear top corner (Other positions from employer) and Prepare hole for wire.
4.8.16 Busbar phase front view (A/B/C) Sorted by Front to back , Top to Bottom , Left to right.
4.8.17 Wear Vinyl Wire End Cap on Wire Terminals use Color-coded by phase not allow color Tape.
• All wire in Trunking , Do not cutting the wires.
• End of control wire must marked on Ferrule.
• Control wire is separated form Cable truncking must orderly by Cable Tie.
4.8.18 Amp Meter (Analog,Digital) can show the current L-L , L-N Type (With CT and Selector Switch).
4.8.19 Volt Meter (Analog,Digital) can show the current L-L , L-N Type (With Selector Switch).
4.8.20 Power Meter (Analog,Digital) can show the current L-L , L-N Type (With Selector Switch).
4.8.21 Signal Lamp can show Status Phase.
4.8.22 Main Circuit Breaker
4.8.22.1 For Electric 400/230 Volt 50 Hz.
4.8.22.2 Frame size not over 400 Amp. type Molded case circuit Breaker , thermal magnatic or solid state trip.
4.8.22.3 Operating mechanism type Manual Operated (or Spring Loaded).
4.8.23 All Equipment must pass Standard as follows.
• ANSI : American National Standard Institute
• BS : British Standard
• CENELEC : Comite European de Normalisation Electrotechnique
• DIN : Deutshes Institute Normung
• IEC : International Electrotechnical Commission
• JIS : Japan Industrial Standard
• NEMA : National Electrical Manufacturers Association
• NESC : National Electrical Safety Code
• NFPA : National Fire Protection Association
• UL : Underwriters Laboratories
• VDE : Verband Deutscher Electrotechniker
• TIS : Thai Industrial Standards
• MEA : Metropolitan Electricity Authority
• PEA : The Provincial Electricity Authority
4.9 Cable, Cable gland, Junction box, Push bottom
• Cable must be of SWA (Steel Wire Armour) type.
• Cable Gland must be of Brass or Stainless available in Hazardous Area Class 1 , Division 1 , Group C , D.
• Junction Box must be of Explosion Proof available in Hazardous Area Class 1 , Division 1 , Group C , D.
• Electrical equipment must be Certification International Standards.
4.10 PLC and PLC Cabinet
4.10.1 PLC cabinet
• PLC Cabinet same height original of oil terminal with lock.
• Install Terminal wiring with Terminal fuse and Circuit breaker.
• Power supply Input 220 VAC , Output 24 VDC size not over 5 A Switching
• Install Surge protection for PLC
• Install Relay (LED) and Socket
• Installation wiring in PVC trunk with core
• Install Bar ground on Power, Instrument
• Install exhaust fans
4.10.2 PLC
4.10.2.1 CPU unit
• Brand "ALLEN BRADLEY" or equivalents (Connect with ALLEN BRADLEY)
• Memory 1G
• High-Speed performance - 0.90 MS/K typical
• Control of up to 4096 Input and Output point
• Online Programming (Includes runtime editing)
• Ethernet 10 Base-T type
• High speed computer communication using TCP/IP
• Built-in realtime clock/calendar
• Advanced Math features-Trigonmetric, PID, Exponential, Floating point and the compute instruction.
• Indirect addressing
• Flash prom provides firm ware upgrades without physically changing eproms
• Key switch-run, Remote, Program (Clear faults)
• Battery backup ram
• Can show Pressure, Temperature realtime
• A local sales representative and after sales service.
4.10.2.2 Power supply unit
• Brand "ALLEN BRADLEY" or equivalents
• Can supply 220 VAC or 110 VAC or 0-30 VDC to CPU
• LED, Lamp indicator
• A local sales representative and after sales service.
4.10.2.3 Chassis
• Brand "ALLEN BRADLEY" or equivalents
• More than 10 slot chassis per CPU 1 set
• A local sales representative and after sales service.
4.10.2.4 I/O / Analog module
• Brand "ALLEN BRADLEY" or equivalents
• I/O more than 16 points per slot
• A local sales representative and after sales service.
4.11 Valve actuator (Absorbent line)
• Motor operate valve (MOV) type
• MOV speed change from open-end less 30 second
• Actuator assembly with mounting and function test
• Connect Field unit on hard wire
• Connect old system (MOV "LIMITTORK" brand)
• Protocal RS232/485 MODBUS type
• Can connect with PLC
• Can input control signal 24 VDC or 125 VAC
• Choose to work in the local and remote type
• LCD indicator for show open percent
• A function self diagnostic without open cover or Verify local switch on actuator screen.
• Can input configuration and parameter without open cover or Verify local switch on actuator screen.
• A password protection for parameter input
• Open-close the valve with manual hand wheel in case of unit breakdown field.
• Cluth motor protection has to be working a normal state
• Torque measurement by Motor speed voltages temperature or Motor current, Fluxs temperature.
• Protection system as follows:
• Auto phase protection & Correction
• Jammed valve
• Motor thermal protection
• ESD
• Can open, close the valve as a percent.
• Absolute encoder, Hall effect, Magnetic pulse, Reed switch show the percent of on - off valve.
• Enclosures IP 68 or better
• Can set torque 40% to 100% or better
• Explosion proof housing
• Can work in Hazadous area class I group D division I
• "LIMITORQUE" or "ROTORK" brand
• 3Phase / 380VAC / 50Hz
• A local sales representative and after sales service.
4.5 Flame Arrester Flame arrester shall be design, manufactured and test in accordance with standard API 2000 or UL525. 4.6 Detonation Arrester Detonation arrester shall be design, manufactured and test in accordance with International standard. 4.7 Hydrocarbon (VOC) Analyzer Hydrocarbon (VOC) Analyzer shall be designed and manufactured in accordance with the emission regulation stipulated by the Pollution Control Department as follows: • Measurement of gas left In organic compounds Using Gas Chromatography. Measured using 18 method (Method 18 : Measurement of Gaseous Organic Compound Emission by Gas Chromatography) as United States Environmental Protection Agency set or • To measure the concentration of gas left. In the form of organic compounds Using a Flame Ionization Analyzer. Measured using 25A method (Method 25A : Total Gaseous Organic Concentration Using a Flame Ionization Analyzer) as United States Environmental Protection Agency set or • To measure the concentration of gas left. In the form of organic compounds Using a Nondispersive Infrared Analyzer. Measured using 25B method (Method 25B : Determination of Total Gaseous Organic Concentration Using a Nondispersive Infrared Analyzer) as United States Environmental Protection Agency set or • Measurement methods and other analysis tools, PCD announced in the Government Gazette. 4.8 Main MCC and Control system 4.8.1 Main MCC Produced by VDE ,IEC ,NEMA or ANSI Standard for 380/220 Volt 3 Phase 4 wire 50 Hz Qualifying requirements NEC Code Article 384 and qualified The EPA to use. 4.8.2 Switch or Circuit Breaker , Magnetic Starter & Overload , Contactor all items must be produced from the same place. 4.8.3 Switch or Circuit Breaker used in low voltage ,Frame size not smaller than required and is resistant short circuit current of not less than specified. 4.8.4 Equipment used in Wiring for motor control include Amp Meter can show value now start and run , Selector Switch can select Remote/Off/Local , Signal lamp can show status Run/Stop/Trip and Hour Meter Available Effectively equivalent to the original equipment. 4.8.5 Main MCC include Switch or Circuit Breaker and Magnetic Starter & Overload is consistent with the Motor Drive for pump control VRU systems as required. 4.8.5.1 Absorbent Supply Pump(Gasoline) 4.8.5.2 Absorbent Return Pump(Gasoline) 4.8.5.3 Condensate Pump 4.8.5.4 Sump Pump 4.8.5.5 Load Panel(LP) Main Power for Essential Load 4.8.5.6 Other Pump 4.8.5.7 Spare Structure details 4.8.6 Frame steel minimum thickness 3 mm. welded or hold with bolt. 4.8.7 Wall steel minimum thickness 2 mm. Corrosion protection process and Spray dried paint overlay. 4.8.8 The device consists of a Busbars , Circuit Breaker , Magnetic Starter & Overload , Rail lines , Terminal , Cable , Metering and base for mounting and must be able to spare for MCC(Up to 25 HP) least 3 sets. 4.8.9 Can be opened The front and rear doors , Part installation Motor control as drawer and have Safety Lock Protection (Block set) make it easier to Maintenance equivalent to the original equipment. 4.8.10 Front doors use soft hinges. 4.8.11 Side walls have ventilation be enough Overlaid with Insect Screen and Dust Filter. 4.8.12 Plastic nameplate and Mimic Bus Diagram on Front doors. 4.8.13 All metal body Corrosion protection process and Spray dried paint overlay (Stove - Enamelled Paint). 4.8.14 Hinged doors must be grounded with copper wire. Technical details 4.8.15 Busbar is Copper purity 98% and must have Ground Bus at the rear bottom corner and Neutral Bus at the rear top corner (Other positions from employer) and Prepare hole for wire. 4.8.16 Busbar phase front view (A/B/C) Sorted by Front to back , Top to Bottom , Left to right. 4.8.17 Wear Vinyl Wire End Cap on Wire Terminals use Color-coded by phase not allow color Tape. • All wire in Trunking , Do not cutting the wires. • End of control wire must marked on Ferrule. • Control wire is separated form Cable truncking must orderly by Cable Tie. 4.8.18 Amp Meter (Analog,Digital) can show the current L-L , L-N Type (With CT and Selector Switch). 4.8.19 Volt Meter (Analog,Digital) can show the current L-L , L-N Type (With Selector Switch). 4.8.20 Power Meter (Analog,Digital) can show the current L-L , L-N Type (With Selector Switch). 4.8.21 Signal Lamp can show Status Phase. 4.8.22 Main Circuit Breaker 4.8.22.1 For Electric 400/230 Volt 50 Hz. 4.8.22.2 Frame size not over 400 Amp. type Molded case circuit Breaker , thermal magnatic or solid state trip. 4.8.22.3 Operating mechanism type Manual Operated (or Spring Loaded). 4.8.23 All Equipment must pass Standard as follows. • ANSI : American National Standard Institute • BS : British Standard • CENELEC : Comite European de Normalisation Electrotechnique • DIN : Deutshes Institute Normung • IEC : International Electrotechnical Commission • JIS : Japan Industrial Standard • NEMA : National Electrical Manufacturers Association • NESC : National Electrical Safety Code • NFPA : National Fire Protection Association • UL : Underwriters Laboratories • VDE : Verband Deutscher Electrotechniker • TIS : Thai Industrial Standards • MEA : Metropolitan Electricity Authority • PEA : The Provincial Electricity Authority4.9 Cable, Cable gland, Junction box, Push bottom • Cable must be of SWA (Steel Wire Armour) type. • Cable Gland must be of Brass or Stainless available in Hazardous Area Class 1 , Division 1 , Group C , D. • Junction Box must be of Explosion Proof available in Hazardous Area Class 1 , Division 1 , Group C , D. • Electrical equipment must be Certification International Standards. 4.10 PLC and PLC Cabinet 4.10.1 PLC cabinet • PLC Cabinet same height original of oil terminal with lock. • Install Terminal wiring with Terminal fuse and Circuit breaker. • Power supply Input 220 VAC , Output 24 VDC size not over 5 A Switching • Install Surge protection for PLC • Install Relay (LED) and Socket • Installation wiring in PVC trunk with core • Install Bar ground on Power, Instrument • Install exhaust fans 4.10.2 PLC 4.10.2.1 CPU unit • Brand "ALLEN BRADLEY" or equivalents (Connect with ALLEN BRADLEY) • Memory 1G • High-Speed performance - 0.90 MS/K typical • Control of up to 4096 Input and Output point • Online Programming (Includes runtime editing) • Ethernet 10 Base-T type • High speed computer communication using TCP/IP • Built-in realtime clock/calendar • Advanced Math features-Trigonmetric, PID, Exponential, Floating point and the compute instruction. • Indirect addressing • Flash prom provides firm ware upgrades without physically changing eproms • Key switch-run, Remote, Program (Clear faults) • Battery backup ram • Can show Pressure, Temperature realtime • A local sales representative and after sales service. 4.10.2.2 Power supply unit • Brand "ALLEN BRADLEY" or equivalents • Can supply 220 VAC or 110 VAC or 0-30 VDC to CPU • LED, Lamp indicator • A local sales representative and after sales service. 4.10.2.3 Chassis • Brand "ALLEN BRADLEY" or equivalents
• More than 10 slot chassis per CPU 1 set
• A local sales representative and after sales service.
4.10.2.4 I/O / Analog module
• Brand "ALLEN BRADLEY" or equivalents
• I/O more than 16 points per slot
• A local sales representative and after sales service.
4.11 Valve actuator (Absorbent line)
• Motor operate valve (MOV) type
• MOV speed change from open-end less 30 second
• Actuator assembly with mounting and function test
• Connect Field unit on hard wire
• Connect old system (MOV "LIMITTORK" brand)
• Protocal RS232/485 MODBUS type
• Can connect with PLC
• Can input control signal 24 VDC or 125 VAC
• Choose to work in the local and remote type
• LCD indicator for show open percent
• A function self diagnostic without open cover or Verify local switch on actuator screen.
• Can input configuration and parameter without open cover or Verify local switch on actuator screen.
• A password protection for parameter input
• Open-close the valve with manual hand wheel in case of unit breakdown field.
• Cluth motor protection has to be working a normal state
• Torque measurement by Motor speed voltages temperature or Motor current, Fluxs temperature.
• Protection system as follows:
• Auto phase protection & Correction
• Jammed valve
• Motor thermal protection
• ESD
• Can open, close the valve as a percent.
• Absolute encoder, Hall effect, Magnetic pulse, Reed switch show the percent of on - off valve.
• Enclosures IP 68 or better
• Can set torque 40% to 100% or better
• Explosion proof housing
• Can work in Hazadous area class I group D division I
• "LIMITORQUE" or "ROTORK" brand
• 3Phase / 380VAC / 50Hz
• A local sales representative and after sales service.
การแปล กรุณารอสักครู่..
4.5 เปลวไฟ Arrester
สายดินเปลวไฟจะต้องมีการออกแบบการผลิตและการทดสอบตามมาตรฐาน API 2000 หรือ UL525.
4.6 ระเบิด Arrester
ดักระเบิดจะต้องได้รับการออกแบบผลิตและทดสอบตามมาตรฐานระหว่างประเทศ.
4.7 ไฮโดรคาร์บอน (VOC)
วิเคราะห์ไฮโดรคาร์บอน(VOC) วิเคราะห์
จะต้องได้รับการออกแบบและผลิตให้สอดคล้องกับกฎระเบียบของการปล่อยก๊าซที่กำหนดโดยกรมควบคุมมลพิษดังนี้•การวัดของก๊าซที่เหลืออยู่ในสารอินทรีย์ใช้แก๊สโครมาโต โดยใช้วิธีการวัด 18
(วิธีที่ 18: การวัดสารประกอบอินทรีย์โดยการปล่อยก๊าซแก๊สโครมาโต)
ในฐานะหน่วยงานของสหรัฐอเมริกาคุ้มครองสิ่งแวดล้อมหรือชุด•การวัดความเข้มข้นของก๊าซซ้าย ในรูปแบบของสารอินทรีย์ใช้เปลวไฟไอออนไนซ์วิเคราะห์ โดยใช้วิธีการวัด 25A
(วิธี 25A: รวมความเข้มข้นของก๊าซอินทรีย์ใช้เปลวไฟวิเคราะห์ไอออนไนซ์)
ในฐานะหน่วยงานของสหรัฐอเมริกาคุ้มครองสิ่งแวดล้อมหรือชุด•การวัดความเข้มข้นของก๊าซซ้าย ในรูปแบบของสารอินทรีย์ใช้วิเคราะห์อินฟราเรด Nondispersive วัดโดยใช้วิธีการ 25B
(วิธี 25B การกำหนดรวมก๊าซอินทรีย์เข้มข้นใช้ Nondispersive อินฟราเรดวิเคราะห์)
ในขณะที่สหรัฐอเมริกาหน่วยงานคุ้มครองสิ่งแวดล้อมชุดหรือ•วิธีการวัดและเครื่องมือวิเคราะห์อื่นๆ ที่กรมควบคุมมลพิษประกาศในราชกิจจานุเบกษา.
4.8 MCC หลักและระบบการควบคุม
4.8 0.1 MCC หลักผลิตโดย VDE, IEC, ANSI หรือ NEMA มาตรฐานสำหรับ 380/220 โวลต์ 3 เฟส 4 สาย 50 เฮิรตซ์ต้องการคัดเลือก NEC รหัสมาตรา 384 และมีคุณสมบัติเหมาะสมที่จะใช้ EPA.
4.8.2 สวิทช์หรือ Circuit Breaker, Starter แม่เหล็กและโอเวอร์โหลด , คอนแทครายการทั้งหมดต้องได้รับการผลิตจากที่เดียวกัน.
4.8.3 สวิทช์หรือ Circuit Breaker ใช้ในแรงดันต่ำขนาดกรอบไม่เล็กกว่าที่จำเป็นและสามารถทนกระแสลัดวงจรได้ไม่น้อยกว่าที่กำหนดไว้.
4.8.4 อุปกรณ์ที่ใช้ในการเดินสายไฟสำหรับ การควบคุมมอเตอร์รวมถึงเครื่องวัดแอมป์สามารถแสดงค่าในขณะนี้เริ่มต้นและเรียกใช้สวิทช์เลือกสามารถเลือกระยะไกล / ปิด / ท้องถิ่น, โคมไฟสัญญาณสามารถแสดงสถานะ Run / Stop / การเดินทางและชั่วโมงมิเตอร์ที่มีจำหน่ายอย่างมีประสิทธิภาพเทียบเท่ากับอุปกรณ์เดิม.
4.8.5 MCC หลัก ได้แก่ สวิทช์หรือเบรกเกอร์และ Starter แม่เหล็กและโอเวอร์โหลดสอดคล้องกับไดรฟ์สำหรับการควบคุมมอเตอร์ปั๊มระบบ VRU ตามที่ต้องการ.
4.8.5.1 ซัพพลายปั๊มดูดซับ (เบนซิน)
4.8.5.2 ดูดซับกลับปั๊ม (เบนซิน)
4.8.5.3 คอนเดนเสทปั๊ม
4.8.5.4 บ่อ
ปั๊มแผงโหลด4.8.5.5 (LP) พลังงานหลักสำหรับการโหลดที่สำคัญ
4.8.5.6 อื่น ๆ ปั๊ม
4.8.5.7
อะไหล่รายละเอียดโครงสร้าง
4.8.6 กรอบเหล็กหนา 3 มมขั้นต่ำ รอยหรือมีไว้กับสายฟ้า.
4.8.7 เหล็กผนังหนาต่ำสุด 2 mm ขั้นตอนการป้องกันการกัดกร่อนและการซ้อนทับสีสเปรย์แห้ง.
4.8.8 อุปกรณ์ประกอบด้วย busbars, เบรกเกอร์, Starter แม่เหล็กและโอเวอร์โหลด, รถไฟ, สถานีเคเบิ้ล, การวัดแสงและฐานสำหรับการติดตั้งและจะต้องสามารถที่จะสำรองไว้สำหรับ MCC (สูงสุด 25 HP) อย่างน้อย 3 ชุด.
4.8.9 สามารถเปิดด้านหน้าและประตูด้านหลังติดตั้งส่วนควบคุมมอเตอร์เป็นลิ้นชักและมีความปลอดภัยในการป้องกันการล็อค (บล็อกตั้งค่า) ให้ง่ายต่อการบำรุงรักษาเทียบเท่ากับอุปกรณ์เดิม.
4.8.10 ประตูด้านหน้า ใช้บานพับอ่อน.
4.8.11 ผนังด้านข้างมีการระบายอากาศที่เพียงพอบุด้วยหน้าจอแมลงและตัวกรองฝุ่น.
4.8.12 ป้ายพลาสติกและเลียนแบบรถแผนภาพที่ประตูด้านหน้า.
4.8.13 ทุกตัวโลหะป้องกันการกัดกร่อนกระบวนการและสเปรย์ซ้อนทับสีแห้ง (เตา -.
เคลือบสี). 4.8.14
ประตูบานพับต้องต่อสายดินกับลวดทองแดงรายละเอียดทางเทคนิค
4.8.15 Busbar คือความบริสุทธิ์ทองแดง 98% และต้องมีรถประจำทางพื้นดินที่มุมล่างด้านหลังและรถประจำทางที่เป็นกลางที่มุมบนด้านหลัง (ตำแหน่งอื่น ๆ ที่มาจาก นายจ้าง) และเตรียมหลุมสำหรับลวด.
4.8.16 Busbar เฟสมุมมองด้านหน้า (A / B / C) เรียงตามด้านหน้าไปด้านหลังบนลงล่างซ้ายไปขวา.
4.8.17 สวมหมวกไวนิลลวด End ได้ที่ขั้วสายไฟใช้ Color- เขียนโดยขั้นตอนการไม่อนุญาตให้เทปสี.
•สายในทุกเดินสายไฟไม่ตัดสายไฟ.
•สิ้นสุดของสายการควบคุมจะต้องทำเครื่องหมายไว้บนปลอกโลหะ.
•สายควบคุมแยกรูปแบบเคเบิ้ล truncking ต้องเป็นระเบียบเรียบร้อยโดย Cable Tie.
4.8.18 เครื่องวัดแอมป์ ( อะนาล็อก, ดิจิตอล) สามารถแสดง LL ปัจจุบัน LN ประเภท (ด้วย CT และสวิทช์เลือก).
4.8.19 โวลต์มิเตอร์ (อนาล็อกดิจิตอล) สามารถแสดง LL ปัจจุบัน LN ประเภท (พร้อมสวิทช์เลือก).
4.8.20 เครื่องวัดพลังงาน ( อะนาล็อก, ดิจิตอล) สามารถแสดง LL ปัจจุบัน LN ประเภท (พร้อมสวิทช์เลือก).
4.8.21 สัญญาณโคมไฟสามารถแสดงสถานะเฟส.
4.8.22 วงจรหลัก Breaker
4.8.22.1 สำหรับไฟฟ้า 400/230 โวลต์ 50 Hz.
4.8.22.2 กรอบ ขนาดไม่เกิน 400 แอมป์ พิมพ์เบรคเกอร์, แม่เหล็กความร้อนหรือการเดินทางของรัฐที่มั่นคง.
4.8.22.3 ประเภทกลไกการดำเนินงานคู่มือการดำเนินการ (หรือฤดูใบไม้ผลิโหลด).
4.8.23 อุปกรณ์ทั้งหมดจะต้องผ่านมาตรฐานดังต่อไปนี้.
• ANSI:
อเมริกันสแตนดาร์ดสถาบันแห่งชาติ• BS: Standard อังกฤษ
• CENELEC: Comite ยุโรป de Normalisation electrotechnique
• DIN: Deutshes สถาบัน Normung
• IEC: International Electrotechnical Commission
ซึ่ง• JIS:
มาตรฐานอุตสาหกรรมญี่ปุ่น• NEMA:
สมาคมแห่งชาติผู้ผลิตไฟฟ้า• NESC:
ความปลอดภัยทางไฟฟ้าแห่งชาติรหัส• NFPA:
การป้องกันอัคคีภัยแห่งชาติสมาคม• UL: Underwriters Laboratories
• VDE: บานด์ดอย Electrotechniker
•มอก:
มาตรฐานผลิตภัณฑ์อุตสาหกรรม•กฟน.: การไฟฟ้านครหลวง•กฟภ. การไฟฟ้าส่วนภูมิภาค 4.9 เคเบิ้ลต่อมเคเบิ้ลกล่องสนธิกดด้านล่าง•เคเบิ้ลจะต้องเป็นSWA (ลวดเหล็กเกราะ) พิมพ์ . •เคเบิ้ลต่อมต้องเป็นทองเหลืองหรือสแตนเลสที่มีอยู่ในพื้นที่อันตรายชั้น 1, ดิวิชั่น 1, กลุ่ม C, D • Junction Box จะต้องเป็นระเบิดที่มีอยู่ในพื้นที่อันตรายชั้น 1, ดิวิชั่น 1, กลุ่ม C, D •ไฟฟ้า อุปกรณ์จะต้องได้รับการรับรองมาตรฐานสากล. 4.10 PLC และบมจคณะรัฐมนตรี4.10.1 ตู้ PLC • PLC คณะรัฐมนตรีเดิมความสูงเดียวกันของสถานีน้ำมันที่มีการล็อค. •ติดตั้งสายไฟกับฟิวส์เทอร์มินัลและเบรกเกอร์. •แหล่งจ่ายไฟป้อนข้อมูล 220 VAC, เอาท์พุท 24 VDC ขนาดไม่เกิน 5 สลับ•ติดตั้งป้องกันกระแสไฟฟ้ากระชากสำหรับPLC •ติดตั้งรีเลย์ (LED) และซ็อกเก็ต•การติดตั้งสายไฟในลำต้นพีวีซีมีแกน•ติดตั้งพื้นบาร์พาวเวอร์, ตราสาร•ติดตั้งพัดลมดูดอากาศ4.10.2 PLC 4.10.2.1 ยูนิต CPU • ยี่ห้อ "ALLEN BRADLEY" หรือเทียบเท่า (เชื่อมต่อกับ ALLEN BRADLEY) •หน่วยความจำ 1G ประสิทธิภาพ•ความเร็วสูง - 0.90 MS / K ทั่วไป•การควบคุมได้ถึง4096 จุดและอินพุตเอาต์พุต•การเขียนโปรแกรมออนไลน์(รวมถึงการแก้ไขรันไทม์) •อีเธอร์เน็ต 10 Base- ประเภท T •การสื่อสารคอมพิวเตอร์ความเร็วสูงโดยใช้ TCP / IP •ในตัวนาฬิกาเรียลไทม์ / ปฏิทิน•คณิตศาสตร์ขั้นสูงมี-Trigonmetric, PID, เอก, จุดลอยตัวและการสอนประมวล. •อ้อมอยู่พรหม•แฟลชให้อัพเกรดเครื่อง บริษัท โดยไม่มีการเปลี่ยนแปลงทางร่างกาย eproms •สวิทช์การทำงานที่สำคัญระยะไกล Program (ล้างความผิดพลาด) •แกะแบตเตอรี่สำรอง•สามารถแสดงความดัน, อุณหภูมิเรียลไทม์•ตัวแทนขายในประเทศและบริการหลังการขาย. 4.10.2.2 หน่วยแหล่งจ่ายไฟ•ยี่ห้อ"ALLEN BRADLEY" หรือเทียบเท่า• สามารถจัดหา 220 VAC หรือ 110 VAC หรือ 0-30 VDC ถึง CPU LED •ตัวบ่งชี้โคมไฟ•ตัวแทนขายในประเทศและบริการหลังการขาย. 4.10.2.3 แชสซี•ยี่ห้อ"ALLEN BRADLEY" หรือเทียบเท่า•มากกว่า10 ตัวถังช่องต่อ CPU 1 ตั้ง•ตัวแทนขายในประเทศและบริการหลังการขาย. 4.10.2.4 I / O / โมดูลอนาล็อก•ยี่ห้อ"ALLEN BRADLEY" หรือเทียบเท่า• I / O มากกว่า 16 จุดต่อช่อง•ตัวแทนขายในประเทศและบริการหลังการขาย. 4.11 วาล์ว ตัวกระตุ้น (สายดูดซับ) •มอเตอร์ทำงานวาล์ว (MOV) ประเภท•การเปลี่ยนแปลงความเร็วMOV จากปลายเปิดที่ 30 สองน้อย•ประกอบอุปกรณ์ขับเคลื่อนกับการทดสอบการติดตั้งและการทำงาน•หน่วยเชื่อมต่อสนามบนลวดยาก•เชื่อมต่อระบบเดิม(MOV "LIMITTORK" แบรนด์) • Protocal RS232 / 485 ประเภท MODBUS •สามารถเชื่อมต่อกับ PLC •สามารถควบคุมสัญญาณอินพุท 24 VDC หรือ 125 VAC •เลือกที่จะทำงานในรูปแบบท้องถิ่นและระยะไกล•ตัวบ่งชี้ที่จอแอลซีดีสำหรับการแสดงร้อยละเปิด•ตัวเองฟังก์ชั่นการวินิจฉัยโดยไม่ปิดบังเปิดหรือตรวจสอบท้องถิ่นสลับบนหน้าจอตัวกระตุ้น. •สามารถกำหนดค่าการป้อนข้อมูลและพารามิเตอร์โดยไม่ปิดบังเปิดหรือตรวจสอบสวิทช์ในท้องถิ่นบนหน้าจอตัวกระตุ้น. ได้•การป้องกันรหัสผ่านสำหรับการป้อนข้อมูลพารามิเตอร์•เปิดปิดวาล์วที่มีล้อมือด้วยตนเองในกรณีของสนามสลายหน่วย. • Cluth ป้องกันมอเตอร์ จะต้องมีการทำงานสภาวะปกติ•การวัดแรงบิดโดยความเร็วของมอเตอร์แรงดันอุณหภูมิหรือมอเตอร์ปัจจุบันอุณหภูมิFluxs. •ระบบการป้องกันดังต่อไปนี้•ป้องกันเฟส Auto & แก้ไข•วาล์วติดขัด•มอเตอร์ป้องกันความร้อน• ESD •สามารถเปิดปิดวาล์ว . เป็นเปอร์เซ็นต์•เข้ารหัสแอบโซลูทผลฮอลล์พัลส์แม่เหล็ก, สวิทช์กกแสดงเปอร์เซ็นต์ของบน. - ปิดวาล์ว•สิ่งห่อหุ้มIP 68 หรือดีกว่า•สามารถตั้งแรงบิด40% ถึง 100% หรือดีกว่า•ที่อยู่อาศัยหลักฐานการระเบิด•สามารถทำงานในพื้นที่ Hazadous ระดับฉันส่วนกลุ่ม D ผม• "LIMITORQUE" หรือ "ROTORK" แบรนด์• 3Phase / 380VAC / 50Hz •ตัวแทนขายในประเทศและบริการหลังการขาย