Hose Degradation Issues
Although the maintenance plan for the hillside and riverside hoses prescribed a regular change-out schedule of 30 days, work orders show that change-out frequency was neither systematic nor predictable. At least three times from 2006 to 2010, phosgene hoses were left in service from 4 to 7 months.