In the first set of tests, the center of the pan was placed a 3.4-m-radial distance
away from the detectors. The response time of each detector was estimated by
utilizing the measured temperatures and velocities of the ceiling jet in conjunction
with the RTI value of the detector assigned through the bench-scale tests.