feeders connected to the same bus as the DG feeder. There are
utilities that install a neutral reactor in the wye winding to
reduce ground current from the DG. The reactor must be
selected such that the feeder remains effectively grounded
when the source breaker (A) trips.
transformer. This can result in tripping at the DG location by
ground overcurrent relaying in the DG transformer neutral.