In the extended SCAE framework, the hidden failure effects analysis
is performed on each power system substation to obtain
possible contingencies resulting from hidden failure outages
as well as their conditional probabilities given the occurrence
of initial system disturbances. Hidden failure contingencies
and other system contingencies are then subject to the three
steps of SCAE methodology: (a) contingency selection/ranking,(b)effects analysis,(c)reliability index computation.