With unit controls set for maximum cooling and maximum fan speed, switch S1 shall be
closed to energize the unit. Within 5 s, leakage current shall be measured using both positions
of switch S2. Following this and using both positions of switch S2, manual switching devices
shall be operated as quickly as possible through all cooling modes, but not in the “OFF”
position, to determine the maximum leakage current condition.