2. Bypass Synchronism-Check Relay - the cam that operates the RS contact is dimensioned to hold that contact in the operated position for four adjacent steps of the stepping switch. Thus, the RSl contact shown closed will be closed for 4 steps and open for the remaining 32 steps of the cycle. The RSl contact is factory adjusted to open on the second step. With this setting, it is closed in the Step #34, LOCKOUT, RESET, and Step #1 positions; and as shown in Figure 6, it is generally employed to bypass the synchronism-check relay during a high-speed reclosure.
2. Bypass Synchronism-Check Relay - the cam that operates the RS contact is dimensioned to hold that contact in the operated position for four adjacent steps of the stepping switch. Thus, the RSl contact shown closed will be closed for 4 steps and open for the remaining 32 steps of the cycle. The RSl contact is factory adjusted to open on the second step. With this setting, it is closed in the Step #34, LOCKOUT, RESET, and Step #1 positions; and as shown in Figure 6, it is generally employed to bypass the synchronism-check relay during a high-speed reclosure.