Bang Pakong Combined Cycle (Unit l-2 Replacement) Project Technical Document Curtain materials shall be resistance to moisture and bacteria such as PVC fiberglass yarn. The consideration of fading, warpage, maintenance, and cleaning shall be required. The curtain shall be a motorized roller blind system type and shall be installed to be concealed in the ceiling. Raised floor or double floor shall be provided at Central Control Room, Equipment Room, and Programming Room/ Sever Room. The observation area shall be arranged on the same floor outside the Central Control Room for observers to catch sight of the Central Control Room Without entering into the room. To achieve unobstructed view of Front Large Screen Panel as well as Control Consoles, interior columns which will obstruct such panel shall be avoided. The Central Control Room, Programming Room/ Server Room, Printer Room, Shift Supervisor’s Room, etc., which shall be arranged in the Central Control Building, shall fulfill functional requirements of the cluster’s design and fire compartment, i.e., interior walls, floors, and ceiling with a minimum of 2-hour fire rating. All openings through fire barriers such as doors, Windows, piping, raceway, and ducts shall also be designed to meet the 2-hour fire ratings requirement. A walkway of a minimum 1.50 m width around the building shall be provided.The general arrangement requirement for Central Control Building shall be served as follows. Design Criteria . Approximated Size (m) Basement Floor First Floor Entrance Hall and Foyer Office Room Electrical Room HVAC Equipment Rooms Battery Room Conference Room Office Room 1 Office Room 2 Pantry Room Storage Room Copy Machine Room Locker Room for Men Locker Room for Women Toilet/ Bathroom for Men Toilet/ Bathroom for Women 3 To be determined 8.0 x 8.0 8.0 x 8.0 16.0 x 24.0 To be determined To be determined 17.0 x 8.0 4.0 x 4.0 4.0 x 8.0 4.0 x 4.0 5.0 x 5.0 1.5 x 2.0 For 10 Lockers For 5 Lockers To be determined referring to Section 2A.9 To be detennined referring to 1 Q1 8 Volume 2 Page 2A-7