2.1.3 The conductor shall be unbroken for the full length of the reels.
2.1.4 Type of the low voltage cables shall be specified by the category of service
as followed:
(1) Cables wirings from Sub-main LV Switchboards or Load Center to the
equipment load shall be PVC insulated cables (THW), and flame retardance.
Lighting cables are also included as specified herein.
(2) Cables wirings from service transformer to Main LV Switchboard and to
sub-main LV Switchboards or to Load Center shall be XLPE insulated cables
(CV) or PVC insulated cables, PVC sheath (NYY), and flame retardance as
indicated on the Drawings.
(3) Cables for life safety equipment shall be fire resistance cables (FR).
(4) Cable wiring for Control circults and interfacing shall be 600V PVC/PVC
(CVV) with/or without shields.