Ig = Ia = 3 × I0 = 32 485 A primary. The secondary current in the generator differential relay
will be 32.5 A. The typical minimum pickup of this class of relay is 0.2–0.4 A so 32.5 A is
sufficient to reliably operate on ground faults even with additional resistance or within the generator
winding.