With reference to Fig. 5, this scheme integrates BF
protection with each ZPR but applies cross-initiation to ensure
the trip decision and the BF determination are performed by
two independent devices based on two independent sets of
current signals. This calls for external BFI signaling but
increases the inherent security of the scheme from a false
current measurement, as compared with the Fig. 3 solution.