1. It appears that several space types were missing in the Baseline Case LPD calculation. Spaces such as restrooms, locker rooms, storage rooms, and mechanical or electrical rooms would be expected to be in a building of this type and size, but are not reported. Please provide the LPDs used for all baseline case spaces, and verify that these reflect the actual space layout of the building. Also, it appears that the reported 29.7% lighting energy savings is too high given the LPDs listed for the baseline versus proposed case, and the building functional areas by space type listed in the EAc1 template. Please verify that the lighting is input correctly, and provide a further explanation justifying any discrepancies between the LPDs and the reported savings.