12.1 General
This section of the specification covers the supply and installation of the thermal and acoustic insulation
required for pipe work, equipment and ductwork.
Preparation of the equipment and application of all insulating materials shall be carried out only by skilled
tradesmen, experienced and competent in this type of work.
In general, insulating materials shall be of best quality in their respective types, and shall have the following
physical properties:
•
High thermal efficiency and low moisture absorption combined with adequate strength to prevent
deterioration under normal operating conditions.
•
Resistance to fire and attack of algae, bacteria, vermin and the growth of mould and fungi.
•
Free from objectionable smells when dry or wet and shall not cause or promote corrosion or
deterioration when in contact with galvanized metal, steel, iron, copper, bronze, brass, aluminium or
P.V.C.
All insulating materials shall be delivered to the site in a dry condition and shall be housed in a dry store
until used.
Prior to the application of insulation, all surfaces shall be thoroughly cleaned of scale, rust, grease, oil and
dirt. The application of the insulating materials to any part of the installation shall not be commenced until all
pressure tests on the relevant part have been completed and approved.
All insulation materials, regardless of the methods of fixing, shall be in close contact with the surfaces to
which they are applied. Edges and ends of insulating sections shall be arranged to butt up close to one
another over the whole insulated surface. Joints of insulation shall be properly sealed. Pressure sensitive
tapes shall not be accepted as joints having mechanical strength.
Allowance for thermal movement shall be provided for in the application of insulation.
12.2 External Duct Insulation
All ductwork shall be insulated with fibre glass. The insulation material shall have a thermal conductivity of
not more than 0.03 W/m K. at 20 degrees Celsius mean temperature
The insulation thickness and density shall be 25 mm. thick, 32 kg/m3 density for supply, return and exhaust
duct in air-conditioned space (including return plenum) unless otherwise specified in the drawings. For duct
installed in non air-conditioned space or not in the return plenum, the insulation thickness and density shall
be 50 mm. thick, 32 kg/m3 density for supply, and 25 mm. thick, 32 kg/m3 density for return and exhaust
duct. The vapour barrier shall consist of double-sided aluminium foil (fire-resistant) with glass fibre
reinforcement and craft-paper. The insulation shall meet the requirements of NFPA 90 A.
For duct installed outdoor, the insulation thickness and density shall be 50 mm. thick, 32 kg/m3 density with
stainless steel Jacket 0.7 mm. thick.
Insulation blankets shall be adhered to ducts by applying fire resistant adhesive over the entire outside area
of the ducts.
Insulation thickness at the pin fastener pressing point shall not be less than 90% of the insulation thickness.
All insulation shall be applied so as to give a neat tidy finished appearance. All sections of insulation shall
be accurately matched for thickness. Steps & undulations in the finished surface will not be accepted. Any
sections having damaged ends or edges will likewise be unacceptable.
12. Duct Insulation
Project 239757 | File TTC Mechanical Specification.docx | 7 March 2014 | Revision 01 | Page 64
All insulation shall fit tight to surfaces to be covered, and all slabs and sections shall be built up close,
butting edges being metered, chamfered or shaped as necessary.
The insulation shall be backed with fiber reinforced aluminum foil vapor barrier. The fiber reinforcing grid
shall not be greater than 10 mm. x 10 mm.
Ductwork shall be insulated from hangers and supports.
Fiberglas shall be adhered to duct with fire resistant adhesive. Adhesive shall be applied so that insulation
conforms to duct surfaces uniformly and firmly.
For ducts up to 450 mm. wide, the insulation shall be wrapped around the duct. For horizontal ducts over
450 mm. metal pins or nylon pins shall be adhered using fire resistant adhesive fixed on the bottom surface
at 400 mm. maximum centers. When insulation shall be wrapped around vertical ducts over 450 mm, the
pins shall be located on all sides of the duct at approximately 300 mm. centers. Protruding ends of pins shall
be cut off flush after clamps have been applied. The vapour barrier facing shall be thoroughly sealed with a
vapour-barrier mastic or tape where the pins have pierced through.
All joints shall be sealed with at least 75 mm. wide vapour barrier tape to provide a continuous external
vapour seal. Prior to the application of tape all contact surfaces of vapour barrier foil shall be wiped clean of
dust and grease using cloth and suitable solvent all in accordance with the manufacturer’s recommendation.
All ductwork insulation shall extend over external flanges and stiffening.
Insulation shall be applied so as to form a continuous heat barrier without gaps, cavities and openings. Care
shall be exercised to ensure that the minimum thickness specified is maintained at corners, protrusions, etc.
At the point of support, specially prepared blocks of hardwood or Styrofoam material must be positioned to
ensure integrity of vapour barrier by bounding the supports to the insulation.
12.3
Internal Duct Insulation
The main supply ducts shall be acoustically lined with fibre glass 25 mm. thick, 32 kg/m3 density with glass
cloth for supply, return and transfer air duct indicated in the drawing.
Dimension of air duct indicated in the drawing is not included thickness of insulation.
12.1 ทั่วไป
ส่วนสเปคครอบคลุมจัดหาและติดตั้งฉนวนกันความร้อน และเสียงที่ต้องการ
งานท่อและอุปกรณ์ท่อ .
เตรียมอุปกรณ์และการประยุกต์ใช้ทั้งหมดวัสดุฉนวนจะดำเนินการเท่านั้นโดยฝีมือช่างที่มีประสบการณ์ และเชี่ยวชาญ
, ในงานประเภทนี้
ในทั่วไปวัสดุฉนวนจะต้องมีคุณภาพที่ดีที่สุดในแต่ละประเภท และจะมีคุณสมบัติทางกายภาพต่อไปนี้
:
-
สูงประสิทธิภาพเชิงความร้อน และความชื้นต่ำ บวกกับความแข็งแรงเพียงพอเพื่อป้องกันการเสื่อมสภาพภายใต้สภาวะปกติ
.
-
ความต้านทานไฟและโจมตีของสาหร่าย แบคทีเรีย พยาธิ และการเจริญเติบโตของเชื้อราและเชื้อรา
-
ฟรีจากกลิ่นที่น่ารังเกียจเมื่อแห้งหรือเปียกและจะไม่ทำให้เกิดการกัดกร่อน หรือส่งเสริมหรือ
เสื่อมสภาพเมื่อสัมผัสกับโลหะสังกะสี , เหล็ก , เหล็ก , ทองแดง , ทองแดง , ทองเหลือง , อลูมิเนียม หรือของเล่น P.V.C .
ทั้งหมดวัสดุฉนวนจะถูกส่งไปยังเว็บไซต์ในสภาพที่แห้ง และจะตั้งอยู่ใน
ร้านบริการจนกว่า ใช้
ก่อนการใช้ฉนวนพื้นผิวจะต้องทําความสะอาดของมาตราส่วน , สนิม , จารบี , น้ำมันและสิ่งสกปรก
. การประยุกต์ใช้วัสดุฉนวนเพื่อใด ๆของส่วนการติดตั้งจะไม่เริ่มจนกว่าการทดสอบ
ความกดดันทั้งหมดในส่วนที่เกี่ยวข้องแล้วเสร็จและได้รับการอนุมัติ
วัสดุฉนวนทั้งหมด โดยไม่คำนึงถึงวิธีการแก้ไข จะอยู่ในการติดต่อใกล้ชิดกับพื้นผิว
ซึ่งพวกเขาจะใช้ขอบและปลายของฉนวนส่วนจะจัดก้นขึ้นใกล้หนึ่ง
อีกทั้งฉนวนพื้นผิว ข้อต่อฉนวนจะถูกผนึก
เทปไวต่อแรงดันจะไม่ได้รับการยอมรับเป็นข้อต่อมีความแข็งแรงเชิงกล
เผื่อความเคลื่อนไหวจะให้ในการใช้ฉนวนกันความร้อน
ซื้อท่อฉนวนกันความร้อนภายนอกทั้งหมดจะถูกหุ้มด้วยท่อไฟเบอร์กลาส วัสดุฉนวนกันความร้อน จะมีค่าการนำความร้อนของ
ไม่เกิน 0.03 W / m . ที่อุณหภูมิ 20 องศาเซลเซียสอุณหภูมิเฉลี่ย
ฉนวนความหนาและความหนาแน่นจะเป็น 25 มม. หนา 32 kg / m3 ความหนาแน่นจัดหา ผลตอบแทน และไอเสีย
ท่อในพื้นที่ปรับอากาศ ( รวมผลตอบแทน Plenum ) นอกจากที่ระบุไว้ในรูป สำหรับท่อ
ติดตั้งในพื้นที่ปรับอากาศหรือไม่ในการกลับมา Plenum , ฉนวนความหนาและความหนาแน่นจะ
เป็น 50 mm หนา 32 kg / m3 ความหนาแน่นในการจัดหา และ 25 มิลลิเมตร หนา 32 kg / m3 ความหนาแน่นสำหรับกลับและท่อ
ประกอบ อุปสรรค จะประกอบด้วยอลูมิเนียมฟอยล์สองหน้า ( ไฟ ) กับเส้นใยเสริมแรง
แก้วและกระดาษงานฝีมือฉนวนกันความร้อนที่จะตอบสนองความต้องการของ NFPA 90 A .
สำหรับท่อที่ติดตั้งกลางแจ้ง , ฉนวนความหนาและความหนาแน่นจะเป็น 50 mm หนา 32 kg / m3
ความหนาแน่นกับสแตนเลสเสื้อ 0.7 มิลลิเมตร หนา
ฉนวนผ้าห่มจะยึดติดกับท่อโดยการประยุกต์ใช้ไฟกาวทนกว่าข้างนอกทั้งหมด
ของท่อ .
ความหนาฉนวนที่ขาสปริงกดจุดจะไม่น้อยกว่า 90% ของฉนวนความหนา
ทั้งหมดฉนวนจะใช้เพื่อให้ประณีตเรียบร้อยเสร็จสิ้นลักษณะที่ปรากฏ ทุกส่วนของฉนวนจะ
จะถูกต้องตรงกับความหนา ขั้นตอน& undulations ในพื้นผิวเสร็จแล้วจะไม่ได้รับการยอมรับ
ใด ๆส่วนปลาย หรือมีความเสียหายขอบจะและไม่เป็นที่ยอมรับ
12 ท่อฉนวน
239757 | แฟ้มโครงการ TTC กล specification.docx | 7 มีนาคม 2014 | แก้ไข 01 | หน้า 64
ทั้งหมดฉนวนจะพอดีแน่นกับพื้นผิวจะครอบคลุมและพื้นทั้งหมดและบางส่วนจะถูกสร้างขึ้นปิด
โขกขอบการวัดมุม , หรือรูปเท่าที่จำเป็น
ฉนวนกันความร้อนจะได้รับการสนับสนุนด้วยการเสริมใยอุปสรรคไอ อลูมิเนียมฟอยล์ ไฟเบอร์เสริมตาราง
จะไม่ถูกมากกว่า 10 มิลลิเมตร x 10 มิลลิเมตร
ท่อจะเป็นฉนวนจากไม้แขวน และสนับสนุน
fiberglas จะยึดติดกับท่อไฟกาวทน กาวจะถูกใช้เพื่อให้สอดคล้องกับพื้นผิวท่อฉนวน
อย่างสม่ำเสมอและ แน่นหนา
สำหรับท่อถึง 450 mm .กว้าง , ฉนวนจะพันรอบท่อ สำหรับท่อแนวนอนมากกว่า
450 มม. หมุดโลหะหรือหมุดไนล่อนจะปฏิบัติตามโดยใช้กาวกันไฟถาวรบนพื้นผิวด้านล่าง
ที่ 400 mm ศูนย์สูงสุด เมื่อฉนวนจะพันรอบท่อแนวตั้งมากกว่า 450 มม.
พินจะตั้งอยู่ในทุกด้านของท่อประมาณ 300 มิลลิเมตร ศูนย์ยื่นปลายเข็มจะ
ถูกตัดออกกดชักโครกหลังจากยึดจะถูกนำมาใช้ ประกอบอุปสรรคซึ่งจะสะอาดปิดผนึกด้วย
ไอด่านยางเรซินหรือเทปที่หมุดเจาะผ่าน
ทุกข้อต่อจะถูกผนึกด้วยอย่างน้อย 75 มิลลิเมตร เทปกั้นไอกว้างเพื่อให้ต่อเนื่องจากภายนอก
ไอแมวน้ำก่อนใช้เทปทุกพื้นผิวสัมผัสของอุปสรรคไอฟอยล์จะเช็ดทำความสะอาดฝุ่นและคราบของ
โดยใช้ผ้าและตัวทำละลายที่เหมาะสมทั้งหมดตามคำแนะนำของผู้ผลิต
ทุกท่อฉนวนจะขยายผ่านครีบภายนอกและทำให้แข็ง .
ฉนวนจะใช้เพื่อฟอร์มต่อเนื่องกั้นความร้อนโดยไม่ต้องช่องว่าง cavities และเปิดตัวการดูแล
ต้องดำเนินการเพื่อให้มั่นใจว่าน้อยที่สุด ความหนาที่ระบุไว้ที่มุม เป็นรอยขรุขระ ฯลฯ
ณจุดสนับสนุน เตรียมเป็นพิเศษบล็อกไม้หรือโฟมวัสดุต้องวาง
มั่นใจความสมบูรณ์ของไออุปสรรคโดยการสนับสนุนให้ฉนวนกันความร้อน
บริการภายในท่อฉนวนท่ออุปทานหลักจะเป็นเสียงเรียงรายด้วยใยแก้ว 25 มม. หนา 32 kg / m3 ความหนาแน่นกับแก้ว
ผ้าสำหรับใส่ ผลตอบแทน และท่ออากาศโอนที่ระบุในแบบ
ขนาดของท่ออากาศที่ระบุในการวาดภาพอยู่ที่ความหนาของฉนวนกันความร้อน
การแปล กรุณารอสักครู่..