Supposing that we now have a change in the capacitance and the dissipation factor of the bushing on phase A, as shown
in Figure 3.(b), the Change Vector (DI) that expresses the displacement of current Ia from its initial value to its final
value is also reflected in the sum current, which is changed in relation to its initial value according to the same Change
Vector DI.