NFPA 13 sec. 8.17.4.1.1 An alarm test connection not less than 1 in. (25 mm) in diameter, terminating in a smooth bore corrosion-resistant orifice, giving a flow equal to or less than one sprinkler of a type having the smallest K factor installed on the particular system, shall be provided to test each water flow alarm device for each system.