This method is prone to misoperate during high-magnitude through faults Transformerground
differential relaying substantially improves transformer ground fault sensitivity and is recommended in [4].
The example described above actually occurred at a paper mill where the fault was caused by human contact.
High-speed protection for this event was extremely important and was provided by the digital ground differential that was recently installed on the transformer.