The Rectifying equipment shall be used with a full float operating battery bank. It shall have facilities for float charging, manual charging and automatic equalizing charging of the battery bank. The voltage level at each operating mode can be adjusted at 2.15 to 2.25 Volts/cell (Float charge) and 2.25 to 2.50 Volts/cell (Equalizing charge) or as recommended by battery manufacturer.