Step II. Database Modification Procedure
In this procedure you will edit and then save the database.
Step 1. On the Configuration Tool main window click on the Screen Objects icon. The Screen
Object window displays.
Step 2. Edit the database (refer to the “Database Object Editing” on page 15 for information).
Step 3. Exit the Configuration Tool and then respond to the Save Changes prompt with a Yes
button click to update the database.
Step 4. Perform the "Step III. Importing the Modified Database Procedure".
Step III. Importing the Modified Database Procedure
Use the applicable procedure to import your modified database back into the ONYXWorks®
system.
Database Import from an External Device
Step 1. On the Configuration PC right click on its PC Monitor and select Backup System Data...
The Browse For Folder window displays.
Step 2. Browse to a Configuration PC folder location and make a new folder (Create New Folder
button) to copy the backup files to.
Step 3. Use Windows Explorer to copy the folder on the Configuration PC to an external storage
device.
Step 4. Exit all the ONYXWorks® system software applications that are running on the
monitoring Workstation except PC Monitor.
Step 5. Right click on the monitoring Workstation’s PC Monitor icon and select Login.
Step 6. Select a User and type in their password (Admin = admin).
Step 7. Right click on the monitoring Workstation’s PC Monitor icon and then select Restore
System Data... from the list of choices. The Browse for Folder window displays.
Step 8. Use the Browse for Folder window’s browse capability to locate the folder on the external
storage device that contains the backup files and select it.
Step 9. Click on the OK button. The edited files are installed on the monitoring Workstation.
Step 10. Restart monitoring Workstation and all of its relative the ONYXWorks® system software
applications.
Step 11. Verify your modified database displays correctly.
Step 12. You have completed "Database Modifications Procedures".
Database Import from a Configuration PC
Step 1. Connect the Configuration PC to the IP network the monitoring Workstation IP network.
Step 2. Start the Configuration PC’s version of the PC Monitor.
Step 3. Export/Import the Database.
• Right click on the PC Monitor icon and then select Export System Data to all
Workstations from the list of choices.
• Use the monitoring Workstation’s version of PC Monitor to Import System Data
operation (select the Configuration PC’s IP address).
Step 4. Go to a monitoring Workstation and verify your modified database displays correctly.
Step 5. You have completed "Database Modifications Procedures".