1.1.9 Load Limiting
Load Limiting prevents the unit from loading beyond
a desired value. 4 compressor units can be load limited
to 50% of the compressors by allowing only 1
compressor per system to run. 6 compressor units
can be load limited to 33% or 66% of the compressors.
The 66% limit would allow up to 2 compressors per
system to run, and the33%limit would allow up to 1
compressor per system to run. No other values of