Fig. 6. Effect of dry bulb temperature on moisture removal
(Conditions: Vs = 0.01 l.s-1, ma = 765 kg.hr-1, Tw = 80○C, Twb = 28○C).
Conversely, the effect of wet bulb temperature while maintaining the dry bulb temperature at 36 ○C is shown in Fig. 7. As shown, higher wet bulb temperatures result in lower concentration increase. This is because air with higher bulb temperature but kept at constant dry bulb temperature contains more moisture.