11. Insufficient information has been provided to justify the large heating, cooling, and pumping energy savings, and the unusually low heat rejection energy consumption in the Baseline Case, and the increase in fan energy between the Proposed and Baseline Case. Please provide sufficient information in Table 1.4 or a supporting narrative to justify these changes in energy consumption between the baseline and proposed case.