3.5 Air conditioning system
To control noise level from air condition, the air velocity is important. To achieve 32dBA at bed head, the FCU must located further way from the bed head. The return duct is recommended. The inner lining is also recommended for both supply and return in order to reduce the noise from the FCU. The air velocity shall be lower than 425fpm at supply register and lower than 510fpm at return register