The project team has provided a clarification narrative, lighting floorplans, fixture schedules, exterior lighting layout, and a site light trespass analysis.
The interior lighting plan show that interior lighting fixtures were located to maintain the maximum candela output, from fixtures near exterior glazing, within the building. The narrative provided states that the three existing light fixtures are just outside of the LEED project boundary. However, the site light trespass analysis shows that illuminance at site boundary will exceed the 0.2 footcandles (2.2 lux) in at least two locations (Exterior Scene 1, Calculation Surface 1, Isolines and Value chart). Therefore this credit cannot be awarded.
The project team has provided a clarification narrative, lighting floorplans, fixture schedules, exterior lighting layout, and a site light trespass analysis. The interior lighting plan show that interior lighting fixtures were located to maintain the maximum candela output, from fixtures near exterior glazing, within the building. The narrative provided states that the three existing light fixtures are just outside of the LEED project boundary. However, the site light trespass analysis shows that illuminance at site boundary will exceed the 0.2 footcandles (2.2 lux) in at least two locations (Exterior Scene 1, Calculation Surface 1, Isolines and Value chart). Therefore this credit cannot be awarded.