Floors
All areas shall be in-situ reinforced concrete slabs, finished in accordance with
Clause 10.0 and supported directly over R.C walls or R.C. beams spanning the
walls.
Where cable voids are required to suit electrical or instruments’ equipment in the
Control Room, the area shall be provided with a full access raised modular flooring
system. Comprising of 600mm square access floor panels set to line and level on
adjustable pedestals placed to suit the 600mm on centres modular grid. The
design shall be based with a load bearing capacity of 10 KN/m2 and a
concentrated load capacity of 5 KN/m2.