Smoke detector spacing: On smooth ceilings, 30 – 60 feet
(9.1 to 18.3 m) between projected beams and not more than
one-half that spacing between a projected beam and a sidewall.
Other spacing may be used depending on ceiling height,
airflow characteristics, and response requirements. See NFPA
72.