120-V step-down transformer of the previous example.
Assume that the input wire is No. 14 AWG copper with
THW insulation, and that it is protected by a 15-A circuit
breaker. The circuit breaker clearly is too large to serve
as the sole protection for the transformer. But, the 15-A
circuit breaker is less than 250% of the transformer fullload
current.