Now in both server rooms are OK.
- Alarming system is ok
- AC controller setup finished and I setup the AC switching every 8 hr.
- Temp & Humid around 22-23 degrees, humid around 45-55%
In the UPS room has a problem right now, last Monday the alarming sensor was broken, because the cable is damage by the door pinch then on the display the humid is always show 20 % anyway I talked and checked with the supplier. We have to replace the sensor. He need the time around 2 weeks. Now I put the small sensor inside this room for the temporary.
For the Ac controller in UPS room already setup and the temp & Humid is OK. The temp around 23 degrees , humid around 45-55 % everyday. Now we check by the small sensor.
I provided a short training to security guys and I put the paper how to do when the alarming is ringing and also the telephone number for contact me and Bell.
Thank you,