2.5.1 Air Ducts: Air ducts shall be constructed of iron, steel, aluminum, copper, concrete, masonry, or
clay tile as per NFPA 90 A.
2.5.2 (i) Duct and pipe insulation, coverings, and linings contained in plenums for buildings of all type
of construction shall comply with NFPA 5000. (ii) Foam plastic insulations, other than duct and
pipe installation, coverings and linings contained in plenums shall comply with NFPA 5000
Plenum Material Combustibility: Material exposed to the airflow shall be noncombustible and
have a maximum smoke developed index of 50 or comply with NFPA 5000.
2.5.4 Gypsum Board Air Ducts: Gypsum board having a maximum flame spread index of 25 without
evidence of continued progressive combustion and a maximum smoke developed index of 50
when tested in accordance with NFPA 255, Standard Method of Test of Surface Burning
Characteristics of Building Materials, shall be permitted to be used for negative pressure
exhaust and return ducts where the temperature of the conveyed air does not exceed 52°C
(125°F) in normal service.
ดาวน์โหลดอากาศท่อ : ท่ออากาศจะถูกสร้างจากเหล็ก , เหล็ก , อลูมิเนียม , ทองแดง , คอนกรีต , อิฐ , กระเบื้องดินหรือ
ตาม NFPA 90 A .
( i ) งานวางท่อและฉนวนกันความร้อนท่อ , ปู , และวัสดุบุผิวที่มีอยู่ใน plenums สำหรับอาคาร
ชนิดทั้งหมดของการก่อสร้างจะสอดคล้องกับ NFPA 5000 ( 2 ) โฟมฉนวน นอกจากท่อและ
ติดตั้งท่อปูและวัสดุบุผิวที่มีอยู่ใน plenums จะสอดคล้องกับ NFPA 5000
combustibility Plenum วัสดุ : วัสดุสัมผัสกับกระแสลมจะ noncombustible
มีควันและพัฒนาดัชนีสูงสุด 50 หรือตาม NFPA 5000
2.5.4 ยิปซัมบอร์ด ท่ออากาศ : ยิปซั่มบอร์ดมีเปลวไฟกระจายดัชนีสูงสุด 25 โดยไม่
หลักฐานต่อการเผาไหม้และควันที่พัฒนาก้าวหน้าสูงสุดของดัชนี 50
เมื่อทดสอบตาม NFPA 255 , วิธีทดสอบของพื้นผิวไหม้
ลักษณะของวัสดุก่อสร้าง จะได้รับอนุญาตให้สามารถใช้แรงดันไอเสียและท่อกลับ
ลบที่อุณหภูมิของการถ่ายทอดอากาศไม่เกิน 52 องศา C
( 125 ° F ) ในการให้บริการปกติ
การแปล กรุณารอสักครู่..