• 59 (of the remaining 92) had documentation errors that were corrected.
• 52 (45 from the 92 remaining; 7 from the 62 deleted) changed to alerts (an alert is a message to the operator that does not use the alarm system to deliver; see chapter 12).
• 50 (of the 47 remaining, some more than one each) had configuration corrections (some aspect of the point needed to be changed to conform to the original engineering design requirements; changes included priority and alarm setting below).
• 26 (of the 47 remaining) had their priority changed.
• 19 (of the 47 remaining) were reduced to 7 alarms.
• 7 (of the 35 remaining) were reduced to a single alert.
• 3 (of the 28 remaining) had the alarm settings changed.
• 2 new alarms were added (making a total of 30 alarms).