Fault at the middle of 13.2-kV winding C
Since the transformer is earthed through a resistor that limits the current for faults
at the transformer 13.2-kV bushings to the rating of the winding, and since the fault
is at the middle of the winding, the fault current is then equal to half the rated value
as follows: