Therefore, a three-phase transformer would be tripped during an internal fault. If one phase experiences a very low second harmonic ratio, the shared harmonic calculated from equation (26) will be large and the second harmonic ratios calculated from equation (27) will be large enough to restrain the differential protection from a false operation.