As this phase is earthed by the fault, no trapped charges will be present at re-energization. However, during the fault an appreciable current will flow through the fault due to capacitive coupling from the two sound phase conductors. This current may prevent the earth-fault from extinguishing resulting into an unsuccessful reclosure, for which extinction of secondary arc is studied.