Bidders shall prepare or obtain sufficient water quality sample data to form the basis of their Bids.
The Project Company shall provide two (2) 100% Service Water Storage Tanks with a total capacity equal to at least twenty-four (24) hours of maximum water consumption by the Plant plus firewater storage required to meet the National Fire Protection Association (NFPA) and the local fire code requirements. Firewater storage and refill requirements shall meet NFPA requirements.