Aeration typically raises the dissolved oxygen content of the raw water. In most cases, this is beneficial since a greater concentration of dissolved oxygen in the water can remove a flat taste. However, too much oxygen in the water can cause a variety of problems resulting from the water becoming supersaturated. Supersaturated water can cause corrosion (the gradual decomposition of metal surfaces) and sedimentation problems. In addition, air binding occurs when excess oxygen comes out of solution in the filter, resulting in air bubbles which harm both the filtration and backwash process