PVC insulated (THW), flame Retardance cable
The cables shall be annealed copper solid or standarded wire with flame
retardance polyvinyl chloride(PVC) insulation material, which has rated not
less then 750V 70 °C, compliance with TIS 11-2531 standard table 4 and
tested compliance with IEC 60332 cat C.
All cable size 6mm² or lager shall be stranded.
Cables wiring inside the luminaries shall not be smaller than 1.0 mm²
specified on the Drawings.
Control wires size shall not be smaller than 1.5 mm²
Cable wiring to the convenience outlets shall not be smaller than 2.5 mm²
as specified on the Drawings.