2 Standard for Testing of acid gas emission shall be conforming to IEC 601034-2
Specification : PVC insulated/ PVC sheathed (NYY) cables
Reference to Contract Document : New Item
Reason of Revision : Missing from the Specification
PVC insulated/ PVC Sheathed (NYY) Cables
(1) The cable shall be annealed copper solid or stranded wire with heat resistant
polyvinyl chloride insulation and sheath material, which has not more than rated
450/750V 70°C compliance with TIS 11-2553 Part 101 Table 3, 4, 5 and 6
(2) All cable size 6 mm² or lager shall be stranded.