6.3.2 Before incorporating in concrete, prepare the aggregate to ensure a difinite and uniform condition of moisture. determine the weight of aggregate to be used in the batch by one of the following procedures:
6.3.2.1 determine the mass of low-absorption aggregates (absorption less than 1.0%) in the room-dry condition with allowance made for the amount of water that will be absorbed from the unset concrete (Note 9).this procedure is particularly useful for coarse aggregate which must be batched as individual sizes; because of the danger of segregation it can be used for fine aggregate only when the fine aggregate is separated into individual size fractions.
NOTE 9 when using aggregates with low absorption in room-dry condition the amount of water that will be absorbed by the aggregates before the concrete sets may be assumed to be 80% of the difference between the 24-h absorption of the aggregates determined by test methods C 127 or C 128,and the amount of water in the pores of the aggregates in their room-dry state, as determined by test method C 566.

6.3.2.2 individual size fractions of aggregate may be weighed separately, recombined into a tared container in the amounts required for the batch, and immersed in water for 24 h prior to use. after immersion the excess water is decanted and the combined weight of aggregate and mixing water determined. allowance shall be made foe the amount of water absorbed by the aggregate. the moisture content of the aggregates may be determined in accordance with test methods C 70 and C 566.
6.3.2.3 the aggregate may be brought to and maintained in a saturated condition, with surface moisture contained in sufficiently small amounts to preclude loss by draining at least 24 h prior to use. when this method is used, the moisture content of the aggregate must by determined to permit calculation of proper quantities of the damp aggregate. the quantity of surface moisture present must be counted as a part of the required amount of mixing water.surface moisture in fine aggregate may by determined in accordance with Test methods C 70 and C 566, making due allowance for the amount of water absorbed.the method outlined here (moisture content slightly exceeding absorption) is particularly useful for fine aggregate. It is used less frequently for coarse aggregate because of the difficulty of accurately determining the moisture content, but if used, each size fraction must be handled separately to ensure that the proper grading is obtained.
6.3.2.4 aggregates, fine or coarse, may be brought to and maintained in a saturated surface-dry condition until batched for use. this method is used primarily to prepare material for batches not exceeding 1/4 ft (0.007 m) in volume.care must be taken to prevent drying during weighing and use.
6.4 Lightweight aggregates the procedures for specific gravity, absorption. and preparation of aggregates mentioned in this practice pertain to materials with normal absorption values. lightweight
0/5000
จาก: -
เป็น: -
ผลลัพธ์ (ไทย) 1: [สำเนา]
คัดลอก!
6.3.2 ก่อนเพจในคอนกรีต เตรียมรวมให้เงื่อนไข difinite และเครื่องแบบของความชื้น กำหนดน้ำหนักของการรวมที่จะใช้ในชุดงาน โดยขั้นตอนต่อไปนี้อย่างใดอย่างหนึ่ง: 6.3.2.1 กำหนดมวลของผลการดูดซึมต่ำ (ดูดซึมน้อยกว่า 1.0%) ในสภาพห้องแห้งกับเบี้ยเลี้ยงทำสำหรับน้ำที่จะดูดซึมจากการยกเลิกการตั้งคอนกรีต (หมายเหตุ 9) .this กระบวน นี้มีประโยชน์อย่างยิ่งสำหรับรวมหยาบซึ่งต้องแบบชุดเป็นขนาดแต่ละ เพราะอันตรายของการแบ่งแยก นั้นสามารถใช้สำหรับการรวมดีเฉพาะเมื่อรวมค่าปรับแบ่งออกเป็นเศษส่วนแต่ละขนาด หมายเหตุ 9 เมื่อใช้เพิ่มการดูดซึมต่ำในสภาพห้องแห้งจำนวนน้ำที่จะดูด โดยการเพิ่มก่อนชุดคอนกรีตอาจถือว่าเป็น 80% ของผลต่างระหว่างดูดซึม 24 h รวมข้อมูลตามวิธีการทดสอบ C 127 หรือ C 128 และจำนวนน้ำในรูขุมขนของผลในสถานะห้องแห้งเป็นไปตามวิธีการทดสอบ C 566 6.3.2.2 ขนาดแต่ละส่วนของการรวมอาจสามารถหนักต่างหาก recombined เป็นคอนเทนเนอร์ tared ใน จำนวนที่จำเป็นสำหรับชุด แช่อยู่ในน้ำใน 24 h ก่อนนำไปใช้ หลังจากแช่ decanted น้ำส่วนเกิน และน้ำหนักรวมรวมและการผสมน้ำขึ้น ส่วนลดจะทำศัตรูจำนวนน้ำดูดซึม โดยรวม ชื้นของผลอาจจะกำหนดตามวิธีการทดสอบ C 70 และ C 566 6.3.2.3 รวมอาจสามารถนำ และรักษาในสภาพอิ่มตัว ความชุ่มชื้นผิวอยู่ในยอดเงินพอเล็กห้ามสูญเสีย โดยการระบายน้ำน้อย 24 h ก่อนใช้ เมื่อใช้วิธีนี้ ต้องโดยมีกำหนดชื้นของรวมการเพื่ออนุญาตให้คำนวณปริมาณรวมชื้นเหมาะสม ปริมาณของความชื้นผิวปัจจุบันต้องนับรวมเป็นส่วนหนึ่งของเงินจำเป็นของผสมความชื้น water.surface รวมดีอาจโดยกำหนดตามวิธีการทดสอบ C 70 และ C 566 ทำครบลดพิเศษสำหรับยอดน้ำ absorbed.the วิธีการอธิบายไว้ที่นี่ (ชื้นเกินดูดซึมเล็กน้อย) มีประโยชน์สำหรับการรวมดี ใช้ไม่บ่อยนักสำหรับรวมหยาบเนื่องจากความยากของการกำหนดเนื้อหาความชื้นได้อย่างถูกต้อง แต่ถ้าใช้ เศษส่วนแต่ละขนาดต้องถูกจัดการแยกต่างหากเพื่อให้แน่ใจว่า จัดเกรดที่เหมาะสมได้รับ 6.3.2.4 ผล ดี หรือ หยาบ อาจสามารถนำไป และได้รับการรักษาในสภาพพื้นผิวแห้งอิ่มตัวจนแบบชุดสำหรับใช้ ใช้วิธีการนี้เพื่อจัดเตรียมวัสดุสำหรับชุดที่ต้องถ่ายไม่เกิน 1/4 ฟุต (0.007 เมตร) ใน volume.care เพื่อไม่ให้แห้งระหว่างการชั่งน้ำหนัก และใช้เป็นหลัก 6.4 น้ำหนักเบารวมขั้นตอนการถ่วง การดูดซึม และการเตรียมผลที่กล่าวถึงในแบบฝึกหัดนี้เกี่ยวข้องกับวัสดุที่มีค่าดูดซึมปกติ น้ำหนักเบา
การแปล กรุณารอสักครู่..
ผลลัพธ์ (ไทย) 2:[สำเนา]
คัดลอก!
6.3.2 Before incorporating in concrete, prepare the aggregate to ensure a difinite and uniform condition of moisture. determine the weight of aggregate to be used in the batch by one of the following procedures:
6.3.2.1 determine the mass of low-absorption aggregates (absorption less than 1.0%) in the room-dry condition with allowance made for the amount of water that will be absorbed from the unset concrete (Note 9).this procedure is particularly useful for coarse aggregate which must be batched as individual sizes; because of the danger of segregation it can be used for fine aggregate only when the fine aggregate is separated into individual size fractions.
NOTE 9 when using aggregates with low absorption in room-dry condition the amount of water that will be absorbed by the aggregates before the concrete sets may be assumed to be 80% of the difference between the 24-h absorption of the aggregates determined by test methods C 127 or C 128,and the amount of water in the pores of the aggregates in their room-dry state, as determined by test method C 566.

6.3.2.2 individual size fractions of aggregate may be weighed separately, recombined into a tared container in the amounts required for the batch, and immersed in water for 24 h prior to use. after immersion the excess water is decanted and the combined weight of aggregate and mixing water determined. allowance shall be made foe the amount of water absorbed by the aggregate. the moisture content of the aggregates may be determined in accordance with test methods C 70 and C 566.
6.3.2.3 the aggregate may be brought to and maintained in a saturated condition, with surface moisture contained in sufficiently small amounts to preclude loss by draining at least 24 h prior to use. when this method is used, the moisture content of the aggregate must by determined to permit calculation of proper quantities of the damp aggregate. the quantity of surface moisture present must be counted as a part of the required amount of mixing water.surface moisture in fine aggregate may by determined in accordance with Test methods C 70 and C 566, making due allowance for the amount of water absorbed.the method outlined here (moisture content slightly exceeding absorption) is particularly useful for fine aggregate. It is used less frequently for coarse aggregate because of the difficulty of accurately determining the moisture content, but if used, each size fraction must be handled separately to ensure that the proper grading is obtained.
6.3.2.4 aggregates, fine or coarse, may be brought to and maintained in a saturated surface-dry condition until batched for use. this method is used primarily to prepare material for batches not exceeding 1/4 ft (0.007 m) in volume.care must be taken to prevent drying during weighing and use.
6.4 Lightweight aggregates the procedures for specific gravity, absorption. and preparation of aggregates mentioned in this practice pertain to materials with normal absorption values. lightweight
การแปล กรุณารอสักครู่..
ผลลัพธ์ (ไทย) 3:[สำเนา]
คัดลอก!
6.3.2 ก่อนที่ผสมผสานในคอนกรีต เตรียมรวมเพื่อให้แน่ใจว่า difinite และสภาพเครื่องแบบของความชื้น กำหนดน้ำหนักรวมที่จะใช้ในชุด โดยหนึ่งในขั้นตอนต่อไปนี้ :
6.3.2.1 กำหนดมวลของมวลการดูดซึมการดูดซึมต่ำ ( น้อยกว่า 10 % ) ในห้องพักบริการเงื่อนไขกับเบี้ยเลี้ยงสำหรับปริมาณของน้ำจะถูกดูดซึมจากล้างคอนกรีต ( หมายเหตุ 3 ) ขั้นตอนนี้จะเป็นประโยชน์โดยเฉพาะอย่างยิ่งสำหรับมวลรวมหยาบซึ่งต้อง batched เป็นขนาดของปัจเจกบุคคล เพราะอันตรายของการแยกสามารถใช้มวลรวมละเอียดเมื่อมวลรวมละเอียดคือ แบ่งออกเป็นเศษส่วน
ขนาดของแต่ละบุคคลหมายเหตุ 9 เมื่อใช้มวลรวมต่ำการดูดซึมในห้องบริการสภาพปริมาณน้ำที่จะถูกดูดซึมโดยมวลรวมก่อนชุดคอนกรีตอาจจะถือว่าเป็น 80% ของความแตกต่างระหว่างการ 24-h ของมวลรวมโดยกำหนดวิธีการทดสอบ C หรือ C 127 128 และปริมาณของน้ำในรูของ มวลรวมในห้อง บริการของรัฐตามที่กำหนดโดยวิธีการทดสอบ C 566 .

6.3.2.2 แต่ละขนาดเศษส่วนของมวลรวมอาจจะหนักอีกต่างหาก tared น้ำนมในภาชนะในปริมาณที่จำเป็นสำหรับแบทช์และแช่ในน้ำเป็นเวลา 24 ชั่วโมงก่อนที่จะใช้ หลังจากแช่น้ำส่วนเกินรินและน้ำหนักรวมของการรวมและผสมน้ำวัดเงินจะทำให้ศัตรูปริมาณน้ำดูดซึมโดยรวม . ความชื้นของวัสดุมวลรวมอาจถูกกำหนดตามวิธีการทดสอบ C 70 C 566 .
6.3.2.3 รวมที่อาจจะมาถึง และรักษาในภาวะอิ่มตัวกับความชื้นผิวที่มีอยู่ในปริมาณที่เล็กพอที่จะขัดขวางการสูญเสียโดยการระบาย อย่างน้อย 24 ชั่วโมง ก่อนใช้งานเมื่อวิธีนี้เป็นวิธีที่ใช้ ความชื้นของมวลรวมโดยต้องกำหนดให้คำนวณปริมาณที่เหมาะสมของชื้นรวม . ปัจจุบันปริมาณของความชื้นที่ผิวต้องถูกนับเป็นส่วนหนึ่งของจํานวนของ water.surface ผสมความชื้นในมวลรวมละเอียดอาจกำหนดตามวิธีการทดสอบ C 70 C 566 ,ทำเนื่องจากเงินจำนวนวิธี absorbed.the น้ำอธิบายไว้ที่นี่ ( เนื้อหาเล็กน้อยเกินการดูดซึมความชื้น ) เป็นประโยชน์อย่างยิ่งสำหรับมวลรวมละเอียด มันใช้น้อยกว่าสำหรับมวลรวมหยาบเพราะความยากของถูกต้องกำหนดความชื้น แต่ถ้าใช้ขนาดแต่ละส่วนจะต้องมีการจัดการแยกต่างหากเพื่อให้แน่ใจว่าระดับที่เหมาะสมจะได้รับ
6.3.2.4 มวลรวมละเอียดหรือหยาบ อาจจะนำ และรักษาในภาวะอิ่มตัวผิวแห้งจน batched สำหรับใช้ วิธีนี้จะใช้เป็นหลักเพื่อเตรียมวัสดุสำหรับชุดไม่เกิน 1 / 4 ฟุต ( 0.017 m ) ใน volume.care ต้องดำเนินการเพื่อป้องกันไม่ให้แห้งระหว่างการชั่งน้ำหนักเบาใช้ .
4 มวลรวมวิธีการแรงโน้มถ่วงเฉพาะการดูดซึมและการเตรียมการของมวลรวมที่กล่าวถึงในการปฏิบัตินี้เกี่ยวข้องกับวัสดุที่มีค่าการดูดซึมปกติ น้ำหนักเบา
การแปล กรุณารอสักครู่..
 
ภาษาอื่น ๆ
การสนับสนุนเครื่องมือแปลภาษา: กรีก, กันนาดา, กาลิเชียน, คลิงออน, คอร์สิกา, คาซัค, คาตาลัน, คินยารวันดา, คีร์กิซ, คุชราต, จอร์เจีย, จีน, จีนดั้งเดิม, ชวา, ชิเชวา, ซามัว, ซีบัวโน, ซุนดา, ซูลู, ญี่ปุ่น, ดัตช์, ตรวจหาภาษา, ตุรกี, ทมิฬ, ทาจิก, ทาทาร์, นอร์เวย์, บอสเนีย, บัลแกเรีย, บาสก์, ปัญจาป, ฝรั่งเศส, พาชตู, ฟริเชียน, ฟินแลนด์, ฟิลิปปินส์, ภาษาอินโดนีเซี, มองโกเลีย, มัลทีส, มาซีโดเนีย, มาราฐี, มาลากาซี, มาลายาลัม, มาเลย์, ม้ง, ยิดดิช, ยูเครน, รัสเซีย, ละติน, ลักเซมเบิร์ก, ลัตเวีย, ลาว, ลิทัวเนีย, สวาฮิลี, สวีเดน, สิงหล, สินธี, สเปน, สโลวัก, สโลวีเนีย, อังกฤษ, อัมฮาริก, อาร์เซอร์ไบจัน, อาร์เมเนีย, อาหรับ, อิกโบ, อิตาลี, อุยกูร์, อุสเบกิสถาน, อูรดู, ฮังการี, ฮัวซา, ฮาวาย, ฮินดี, ฮีบรู, เกลิกสกอต, เกาหลี, เขมร, เคิร์ด, เช็ก, เซอร์เบียน, เซโซโท, เดนมาร์ก, เตลูกู, เติร์กเมน, เนปาล, เบงกอล, เบลารุส, เปอร์เซีย, เมารี, เมียนมา (พม่า), เยอรมัน, เวลส์, เวียดนาม, เอสเปอแรนโต, เอสโทเนีย, เฮติครีโอล, แอฟริกา, แอลเบเนีย, โคซา, โครเอเชีย, โชนา, โซมาลี, โปรตุเกส, โปแลนด์, โยรูบา, โรมาเนีย, โอเดีย (โอริยา), ไทย, ไอซ์แลนด์, ไอร์แลนด์, การแปลภาษา.

Copyright ©2024 I Love Translation. All reserved.

E-mail: