Check for individuak purge point solenoids not energized or stuck closed.Check for closed shut-offvalves. Verfty proper operation of the foul gas solenoid valve(#4).To check for a sticking solenoid valve,use the manual-opening stem to temporarily open the valve.Observe if the pressure increases to condensing pressure.Also,ensure that the plastic shipping cap has been removed from the foul gas line flange.