2. Quality Assurance:
a. Qualifications: Each component and product is to be inbound and outbound tested before shipment in accordance with ISO 9001:2000 test procedures.
b. Output Verification: Independent certified testing shall indicate that when Emitter first installed total output per one inch arc length shall not be less than 9 W/cm2, at one meter, in a 500 fpm airstream of 50 F, and at end of manufactures tube warrantee period, or 9000 hours, which ever is longer, shall have output per one inch arc length not be less than 4 W/cm2 at one meter, in a 500 fpm airstream of 50 F.
c. Dose On the Down Stream Coil Face At Extremities: The UVC dose at the extreme edges of the coil shall not be less than 750 W/cm2,
2. Quality Assurance:a. Qualifications: Each component and product is to be inbound and outbound tested before shipment in accordance with ISO 9001:2000 test procedures. b. Output Verification: Independent certified testing shall indicate that when Emitter first installed total output per one inch arc length shall not be less than 9 W/cm2, at one meter, in a 500 fpm airstream of 50 F, and at end of manufactures tube warrantee period, or 9000 hours, which ever is longer, shall have output per one inch arc length not be less than 4 W/cm2 at one meter, in a 500 fpm airstream of 50 F.c. Dose On the Down Stream Coil Face At Extremities: The UVC dose at the extreme edges of the coil shall not be less than 750 W/cm2,