- Warning Sign provided in accordance with EIT Standard or Quality and
Safety Development Division Standard (EGAT).
- Fire protection system : Fire alarm detectors, (aspirated smoke detector, video
image smoke detector system and optical beam smoke detector), fire alarm
system, all accessories shall be in accordance with the applicable
requirements set forth in the latest edition of the following codes and
standards:
- NFPA 70: National Electrical Code.
- NFPA 72 : National Fire Alarm Code.
- EGAT's Standard Design Manual of Fire Protection and Suppression for
Substation ( ~~m.nl'l1~1'U1111arnrnurntiat1eMnmb'1:t;'i:t;ruei'Af11i'v?1mUl ~-W1bb 1~~~ 11111 ~-W1~1v~~l'lbb '1-i~
tJ'i:t;b'Vlf'l1vm)
36.3 230 kV GIS Bushing support structure foundation
36.4 115 kV GIS Bushing support structure foundation
36.5 230 kV GIB support structure foundation
36.6 115 kV GIB support structure foundation
36.7 Fire wall conformed to NFPA 850.
36.8 30 m Telecommunication tower foundation(WSA).
36.9 Remote control (shall be controlled from either the control room or the guard
house) and door phone system for main entrance gate.
36.10 Road and drainage system.
36.11 Drainage system for cable trench.
36.12 Water supply system.
36.13 Foam house and accessories.
36.14 Fire pump house.
36.15 Fire pump system in conformity with NFPA 14, 20, 24, 72
36.16 Oil separator (volume of oil 85 cu.m.)
- The contractor shall make an Oil separator design calculation in
accordance with " IEEE STD-979-1994 (R2004)" ( IEEE Guide for
Substation Fire Protection), " IEEE STD-980-1994 (R2001)" ( IEEE
Guide for containment and control of oil spills in substation ) and "
Wastewater Quality Standard" of Pollution Control Department, Ministry
of Natural Resources and Environment.
- Warning Sign provided in accordance with EIT Standard or Quality andSafety Development Division Standard (EGAT).- Fire protection system : Fire alarm detectors, (aspirated smoke detector, videoimage smoke detector system and optical beam smoke detector), fire alarmsystem, all accessories shall be in accordance with the applicablerequirements set forth in the latest edition of the following codes andstandards:- NFPA 70: National Electrical Code.- NFPA 72 : National Fire Alarm Code.- EGAT's Standard Design Manual of Fire Protection and Suppression forSubstation ( ~~m.nl'l1~1'U1111arnrnurntiat1eMnmb'1:t;'i:t;ruei'Af11i'v?1mUl ~-W1bb 1~~~ 11111 ~-W1~1v~~l'lbb '1-i~tJ'i:t;b'Vlf'l1vm)36.3 230 kV GIS Bushing support structure foundation36.4 115 kV GIS Bushing support structure foundation36.5 230 kV GIB support structure foundation36.6 115 kV GIB support structure foundation36.7 Fire wall conformed to NFPA 850.36.8 30 m Telecommunication tower foundation(WSA).36.9 Remote control (shall be controlled from either the control room or the guardhouse) and door phone system for main entrance gate.36.10 Road and drainage system.36.11 Drainage system for cable trench.36.12 Water supply system.36.13 Foam house and accessories.36.14 Fire pump house.36.15 Fire pump system in conformity with NFPA 14, 20, 24, 7236.16 Oil separator (volume of oil 85 cu.m.)- The contractor shall make an Oil separator design calculation inaccordance with " IEEE STD-979-1994 (R2004)" ( IEEE Guide forSubstation Fire Protection), " IEEE STD-980-1994 (R2001)" ( IEEEGuide for containment and control of oil spills in substation ) and "Wastewater Quality Standard" of Pollution Control Department, Ministryof Natural Resources and Environment.