I would like to send attached files for Air conditioners.
I combined “Air conditioner equipment data (from you)” and “NSA layout drawings data”.
I will attach drawings that I made modifications.
About [BL Weighing and Mixing room] pdf file
*Duct layout is good in your drawings.
*Your drawings, reversed the position of the chiller 01 and chiller 02?
I think drawing I wrote is correct.
*Equipment number of your drawings has been used in existing facilities.
Please modification to number, which describes the equipment number in the drawing.
*CHP number is OK.
About [PF-Press room 1 and 2] pdf file
*Duct layout of room 1 is OK in your drawings.
*Duct layout of room 2 is Not good in your drawings.
See the attached file, please modification to your drawings.
*Wall thickness was 80mm.
*How do you dispose of the drain? (Tank and pump or Pit and pump or…)
Did not write about it, In your drawings.
*Equipment number of your drawings has been used in existing facilities.
Please modification to number, which describes the equipment number in the drawing.
*Position of chiller has largely shifted in your drawings.
See the attached file, please modification to your drawings.
About [Reference drawings for Air conditioners] LT-2004 type
*This is a master data.