Moreover, this error will change as gas pressure inside the vessel changes, so it cannot simply
be “calibrated away” by a static zero shift within the instrument. The only way to hydrostatically
measure liquid level inside an enclosed (non-vented) vessel is to continuously compensate for gas
pressure